To configure this option with the Touch Pilot™ display:

To configure this option with the Navigator™ display:

In the example in Fig. 21 using Return Water Temperature

Reset, the chilled water temperature will be reset by 5° F

(2.8° C) when the Fluid Temperature Difference is 2° F

(1.1° C) and 0° F (0° C) reset when the Temperature Difference

is 10° F.
SPACE TEMPERATURE RESET — The control system is

also capable of temperature reset based on space temperature

(SPT). An accessory sensor must be used for SPT reset

(33ZCT55SPT). The Energy Management Module (EMM) is

also required for temperature reset using space temperature.

To use Space Temperature Reset, four variables must be

configured. Cooling Reset Type (Cooling Reset Select, CRST)

must be enabled. The space temperature at which no tempera-

ture reset is required, Space T No Reset Temp (Space T No

Reset Value, CRS1) must be set. The space temperature at

which full temperature reset is required, Space T Full Reset

Temp (Space T Full Reset Value, CRS2) must be set. Finally,

the amount of temperature reset desired, Degrees Cool Reset

(Cooling Reset Deg. Value, DRGC), must be set.

To configure this option with the Touch Pilot display:

To configure this option with the Navigator display:

In the space temperature reset example in Fig. 22, 0° F

(0° C) chilled water set point reset at 72 F (22.2 C) space

temperature and 6° F (3.3° C) reset at 68 F (20.0 C) space

temperature.
4-20 mA TEMPERATURE RESET — The control system is

also capable of temperature reset based on an externally pow-

ered 4 to 20 mA signal. The Energy Management Module

(EMM) is required for temperature reset using a 4 to 20 mA

signal.

To use 4-20 mA Temperature Reset, four variables must be

configured. Cooling Reset Type (Cooling Reset Select, CRST)

must be enabled. The milliamp signal at which no temperature

reset is required, Current No Reset Value (Current No Reset

Value, CRV1), must be set. The milliamp signal at which full

temperature reset is required, Current Full Reset Value (Cur-

rent Full Reset Value, CRV2), must be set. Finally, the

amount of temperature reset desired, Degrees Cool Reset

(Cooling Reset Deg. Value, DRGC), must be set.

To configure this option with the Touch Pilot™ display:

To configure this option with the Navigator™ display:

In the example in Fig. 23, at 4 mA no reset takes place and

at 20 mA, 5° F (2.8° C) chilled water set point reset is required.

DISPLAY NAME

PATH

LINE NO.

VALUE

Cooling Reset
Select

Main
Menu

Config

USER

19

Default =0
(No Reset)
2 (Delta T)

Delta T No
Reset Temp

Main
Menu

Setpoint

SETPOINT

7

Default =
0 F (0 C)

Delta T Full
Reset Temp

Main
Menu

Setpoint

SETPOINT

8

Default =
0 F (0 C)

Cooling Reset
Deg. Value

Main
Menu

Setpoint

SETPOINT

13

Default =
0 F (0 C)

ITEM

ITEM EXPANSION

PATH

VALUE

CRST

Cooling Reset
Type

Configuration

RSET

Default =
No Reset
Delta T Temp

CRT1

Delta T No
Reset Temp

Setpoints

COOL

Default =
0 F (0 C)

CRT2

Delta T Full
Reset Temp

Setpoints

COOL

Default =
0 F (0 C)

DGRC

Degrees Cool
Reset

Setpoints

COOL

Default =
0 F (0 C)

DISPLAY NAME

PATH

LINE

NO.

VALUE

Cooling Reset
Select

Main Menu

Config

USER

19

Default =0
(No Reset)
4 (Space Temp)

Space T No
Reset Value

Main Menu

Setpoint

SETPOINT

11

Default =
14 F (–10 C)

Space T Full
Reset Value

Main Menu

Setpoint

SETPOINT

12

Default =
14 F (–10 C)

Cooling Reset
Deg. Value

Main Menu

Setpoint

SETPOINT

13

Default =
0 F (0 C)

ITEM

ITEM EXPANSION

PATH

VALUE

CRST

Cooling Reset Type

Configuration

RSET

Default =
No Reset
Space Temp

CRS1

Space T No Reset
Temp

Setpoints

COOL

Default =
14 F (–10 C)

CRS2

Space T Full Reset
Temp

Setpoints

COOL

Default =
14 F (–10 C)

DGRC

Degrees Cool Reset

Setpoints

COOL

Default =
0 F (0 C)

CAUTION

Care should be taken when interfacing with other control

systems due to possible power supply differences such as a

full wave bridge versus a half wave rectification. Connec-

tion of control devices with different power supplies may

result in permanent damage. The ComfortLink™ controls

incorporate power supplies with half wave rectification. A

signal isolation device should be utilized if the signal gen-

erator incorporates a full wave bridge rectifier.

DISPLAY NAME

PATH

LINE NO.

VALUE

Cooling Reset
Select

Main Menu

Config

USER

19

Default =0
(No Reset)
3 (4-20mA
Control)

Current No
Reset Value

Main Menu

Setpoint

SETPOINT

9

Default = 0.0

Current Full
Reset Value

Main Menu

Setpoint

SETPOINT

10

Default = 0.0

Cooling Reset
Deg. Value

Main Menu

Setpoint

SETPOINT

13

Default =
0.0 F (0.0 C)

ITEM

ITEM EXPANSION

PATH

VALUE

CRST

Cooling Reset
Type

Configuration

RSET

Default =
No Reset
4-20mA Input

CRV1

Current No
Reset Temp

Setpoints

COOL

Default = 0.0

CRV2

Current Full
Reset Temp

Setpoints

COOL

Default = 0.0

DGRC

Degrees Cool
Reset

Setpoints

COOL

Default = 0.0