69 table 49 — alarm codes – Carrier AQUAFORCE 30XW150-400 User Manual

Page 69

Advertising
background image

69

Table 49 — Alarm Codes

LEGEND

PREFIX

CODE

SUFFIX

CODE

ALARM

NUMBER

ALARM DESCRIPTION

REASON FOR ALARM

ACTION TAKEN

BY CONTROL

RESET

TYPE

PROBABLE CAUSE

th

01

1

Cooler Entering Fluid
Thermistor

Temperature measured

by the controller is

outside of the range

of –40 F to 245 F

Unit be shut down or

not allowed to start

Automatic

Faulty Sensor,

wiring error or failed

main base board

02

2

Cooler Leaving Fluid
Thermistor

03

3

Circuit A Defrost Thermistor

None

Automatic

Configuration error

04

4

Circuit B Defrost Thermistor

06

5

Condenser Entering
Fluid Thermistor

07

6

Condenser Leaving
Fluid Thermistor

08

7

Reclaim Condenser
Entering Thermistor

09

8

Reclaim Condenser
Leaving Thermistor

11

10

Master/Slave Common Fluid
Thermistor

Dual chiller deacti-

vated. Master and

slave machines

operate in stand-

alone mode

Automatic

Faulty Sensor,

wiring error or failed

main base board

12

11

Circuit A Suction Gas
Thermistor

Circuit shut down or

not allowed to start

Automatic

Faulty Sensor,

wiring error, failed

EXV or CPM board

13

12

Circuit B Suction Gas
Thermistor

15

14

Circuit A Discharge Gas
Thermistor

16

15

Circuit B Discharge Gas
Thermistor

18

17

Circuit A Condenser Sub-
cooling Liquid Thermistor

Not supported

Automatic

Configuration error

19

18

Circuit B Condenser Sub-
cooling Liquid Thermistor

21

19

Space Temperature
Thermistor

Alarm tripped

Automatic

Faulty Sensor, wiring

error, failed EMM

board

23

20

Cooler heater feedback
thermistor

None

Automatic

Configuration error

24

21

Circuit A Economizer Gas
Thermistor

Circuit economizer

function disabled

Automatic

Faulty Sensor,

wiring error, failed

EXV board

25

22

Circuit B Economizer Gas
Thermistor

Pr

01

26

Circuit A Discharge
Transducer

Measured voltage is

0 vdc or SST > EWT and

EXV < 50% for 1 minute

Circuit shut down or

not allowed to start

Automatic

Faulty transducer,
wiring error, failed

main base board or

fan board

02

27

Circuit B Discharge
Transducer

04

29

Circuit A Suction Transducer

05

30

Circuit B Suction Transducer

07

32

Circuit A Reclaim Pump-
down Pressure Transducer

None

Automatic

Configuration error

08

33

Circuit B Reclaim Pump-
down Pressure Transducer

10

34

Circuit A Oil Pressure
Transducer

Circuit shut down or

not allowed to start

Automatic

Faulty transducer,
wiring error, failed

CPM board

11

35

Circuit B Oil Pressure
Transducer

13

37

Circuit A Economizer
Pressure Transducer

Measured voltage is

0 vdc

14

38

Circuit B Economizer
Pressure Transducer

CCN

Carrier Comfort Network

®

MLV

Minimum Load Valve

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

EMM

Energy Management Module

MTA

Must Trip Amps

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

HPS

High Pressure Switch