Appendix b — navigator™ display tables (cont), Mode — pressure mode — inputs – Carrier AQUAFORCE 30XW150-400 User Manual

Page 110

Advertising
background image

110

APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — PRESSURE

MODE — INPUTS

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

STATUS

CCN TABLE

CCN POINT

PAGE

NO.

PRC.A

CIRCUIT A PRESSURES

DP.A

Discharge Pressure Cir A

XXX.X
(psig/kPa)

CIRCA_AN

DP_A

56

SP.A

Suction Pressure Circ A

XXX.X
(psig/kPa)

CIRCA_AN

SP_A

OP.A

Oil Pressure Circ A

XXX.X
(psig/kPa)

OP_A

DOP.A

Oil Pressure Diff A

XXX.X
(psig/kPa)

DOP_A

ECP.A

Economizer Pressure A

XXX.X
(psig/kPa)

ECON_P_A

PRC.B

CIRCUIT B PRESSURES

DP.B

Discharge Pressure Cir B

XXX.X
(psig/kPa)

CIRCB_AN

DP_B

56

SP.B

Suction Pressure Circ B

XXX.X
(psig/kPa)

CIRCB_AN

SP_B

OP.B

Oil Pressure Circ B

XXX.X
(psig/kPa)

OP_B

DOP.B

Oil Pressure Diff B

XXX.X
(psig/kPa)

DOP_B

ECP.B

Economizer Pressure B

XXX.X
(psig/kPa)

ECON_P_B

PRC.C

CIRCUIT A PRESSURES

DP.C

Discharge Pressure Cir C

XXX.X
(psig/kPa)

CIRCC_AN

DP_C

56

SP.C

Suction Pressure Circ C

XXX.X
(psig/kPa)

CIRCC_AN

SP_C

OP.C

Oil Pressure Circ C

XXX.X
(psig/kPa)

OP_C

DOP.C

Oil Pressure Diff C

XXX.X
(psig/kPa)

DOP_C

ECP.C

Economizer Pressure C

XXX.X
(psig/kPa)

ECON_P_C













ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

STATUS

CCN TABLE

CCN POINT

PAGE

NO.

GEN.I

GENERAL INPUTS

ONOF

On Off Switch

OPEN/CLSE

STATEGEN

ONOF

LOCK

Cooler Interlock

OPEN/CLSE

STATEGEN

LOCK_1

44

COND

Condenser Flow Switch

OPEN/CLSE

Not supported.

STATEGEN

CONFLOW

DLS1

Demand Limit Switch 1

OPEN/CLSE

STATEGEN

LIM_SW1

39, 40

DLS2

Demand Limit Switch 2

OPEN/CLSE

STATEGEN

LIM_SW2

39, 40

ICE.D

Ice Done

OFF/ON

STATEGEN

ICE_SW

DUAL

Dual Setpoint Switch

OFF/ON

STATEGEN

SETP_SW

ELEC

Electrical Box Safety

OPEN/CLSE

Not supported.

STATEGEN

ELEC_BOX

PUMP

Pump Run Feedback

OPEN/CLSE

Not supported.

STATEGEN

PUMP_DEF

OCCS

Occupancy Override Swit

OFF/ON

STATEGEN

OCC_OVSW

HC.SW

Heat Cool Switch Status

OFF/ON

STATEGEN

HC_SW

RLOC

Remote Interlock Switch

OPEN/CLSE

STATEGEN

REM-LOCK

OIL.A

Oil Level Circuit A

LOW/HIGH

STATEGEN

OIL_L_A

OIL.B

Oil Level Circuit B

LOW/HIGH

STATEGEN

OIL_L_B

OIL.C

Oil Level Circuit C

LOW/HIGH

STATEGEN

OIL_L_C

CUR.A

Motor Current Circuit A

XXX.X (amps)

0-600

STATEGEN

CURR_A

CUR.B

Motor Current Circuit B

XXX.X (amps)

0-600

STATEGEN

CURR_B

CUR.C

Motor Current Circuit C

XXX.X (amps)

0-600

STATEGEN

CURR_C

DMND

4-20 mA Demand Signal

XXX.X (mA)

4 to 20

STATEGEN

LIM_ANAL

RSET

4-20 mA Reset/Setpoint

XXX.X (mA)

4 to 20

STATEGEN

SP_RESET