71 table 49 — alarm codes (cont) – Carrier AQUAFORCE 30XW150-400 User Manual

Page 71

Advertising
background image

71

Table 49 — Alarm Codes (cont)

LEGEND

PREFIX

CODE

SUFFIX

CODE

ALARM

NUMBER

ALARM DESCRIPTION

REASON FOR ALARM

ACTION TAKEN

BY CONTROL

RESET

TYPE

PROBABLE CAUSE

P

11

77

Circuit A Low Suction
Superheat

EXV<5% and either the

suction superheat is less

than the set point by at
least 5 F or the suction

temperature is greater

than MOP set point for

more than 5 minutes

Circuit shut down

Manual

Faulty transducer,

faulty wiring, faulty

thermistor, faulty EXV,

or incorrect

configuration

12

78

Circuit B Low Suction
Superheat

14

80

Interlock Failure

Lockout Switch Closed

Unit shut down or

not allowed to start

Automatic

Lockout Switch Closed

on EMM board

28

81

Electrical Box Thermostat
Failure/Reverse Rotation

External pump interlock

open

Unit shut down or

not allowed to start

Automatic

External pump off.

Faulty jumper wiring

when channel not used

29

82

Loss of communication with
System Manager

Loss of communication
with an external control

device for more than

2 minutes

Unit change to

stand-alone

operation

Automatic

Faulty communication

wiring, no power

supply to the external

controller

30

83

Master/Slave communication
Failure

Communication between

the master and slave

machines lost

Unit change to

stand-alone

operation

Automatic

Faulty communication

wiring, no power or

control power to the

main base board of

either module

67

84

Circuit A Low Oil Pressure

Oil pressure and suction

pressure differential is
less than the set point

Circuit shut down

Automatic, first

occurrence in

24 hours;

manual if

multiple alarms
within 24 hours

Plugged oil filter, faulty

oil transducer, oil check
valve stuck, plugged oil

strainer

68

85

Circuit B Low Oil Pressure

70

87

Circuit A Max Oil Filter Differ-
ential Pressure

Difference between dis-
charge pressure and oil

pressure is greater than

50 psi for more than

30 seconds

Circuit shut down

Manual

Plugged oil filter,

closed oil valve, bad oil

solenoid, oil check

valve stuck, faulty oil

pressure transducer

71

88

Circuit B Max Oil Filter Differ-
ential Pressure

84

90

Circuit A High Oil Filter Drop
Pressure

Difference between dis-
charge pressure and oil

pressure is greater than

30 psi for more than

5 minutes

Alert generated

Manual

Plugged oil filter

85

91

Circuit B High Oil Filter Drop
Pressure

75

93

Circuit A Low Oil Level

Oil level switch open

Circuit shut down or

not allowed to start

Automatic, first

occurrence in

24 hours;

manual if

multiple alarms
within 24 hours

Low oil level, faulty

switch, wiring error,

failed CPM board, oil

solenoid stuck open

76

94

Circuit B Low Oil Level

MC

nn

96

Master chiller configuration
error Number 01 to nn

Wrong or incompatible

configuration data

Unit not allowed to

start in Master-slave

control

Automatic

Configuration error

FC

n0

97

No factory configuration

No Configuration

Unit not allowed to

start

Automatic

Configuration error

nn

98

Illegal factory configuration
Number 01 to 04

Wrong or incompatible

configuration data

Unit not allowed to

start

Automatic

Configuration error

P

31

99

Unit is in CCN emergency
stop

Emergency stop com-

mand has been received

Unit shut down or

not allowed to start

Automatic

Carrier Comfort

Network

®

Emergency

Stop command

received

32

100

Cooler pump #1 fault

Pump interlock status
does not match pump

status

Unit shuts down, if

available, another

pump will start

Manual

Faulty contacts, wiring

error or low control

voltage. Configuration

error.

33

101

Cooler pump #2 fault

15

102

Condenser Flow Switch
Failure

None

Manual

Configuration error,

faulty wiring or external

pump off

34

103

Circuit A Reclaim Operation
Failure

None

Manual

Configuration error

35

104

Circuit B Reclaim Operation
Failure

37

105

Circuit A — High condensing
temperature out of compres-
sor envelope

Multiple capacity over-

rides due to high

saturated discharge

temperature

Circuit shut down

Automatic

Low or restricted

condenser water flow.

Fouled condenser

tubes.

38

106

Circuit B — High condensing
temperature out of compres-
sor envelope

CCN

Carrier Comfort Network

®

MLV

Minimum Load Valve

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

EMM

Energy Management Module

MTA

Must Trip Amps

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

HPS

High Pressure Switch