LIMITED ACCESS PANEL — This configuration is used to

specify the limited access password.
Allowable Entries: 0 through 9999
Default Value:

2222

ACTIVE LANGUAGE — This configuration is used to spec-

ify the display’s active language. All translatable text will be

displayed in this language.
Allowable Entries: 0 (English), 1 (alternate, installed by user)
Default Value:

0

TIME FORMAT — This configuration is used to specify the

format for display of time.
Allowable Entries: 0 = H:MM AM/PM without leading zero

1 = HH:MM with leading zero when

necessary

Default Value:

0

DATE FORMAT — This configuration is used to specify the

format for display of date.
Allowable Entries: 0 = MM-DD-YYYY with leading zero

when necessary
1 = DD-MM-YYYY with leading zero

when necessary
2 = YYYY-MM-DD

Default Value:

0

UNITS BASE — This configuration is used to specify the for-

mat of the units of measure.
Allowable Entries: U.S.

Metric

Default Value:

U.S.

CONTRAST CONTROL — This configuration is used to en-

able or disable the display’s auto contrast adjustment feature.

When enabled, the display’s contrast will be automatically ad-

justed as required, based on temperature.
Allowable Entries: Manual

(Auto Contrast Adjustment Disabled)
Auto
(Auto Contrast Adjustment Enabled)

Default Value:

Auto

NETWORK MODE — This configuration is used to set the

display’s operating mode. For additional information on oper-

ating mode, refer to Display in the Table Setup Menu. This de-

cision will be ignored and the mode will default to Equipment

when the display is connected to a device (the LEN Bus).
NOTE: A power cycle is required for this decision to take

effect.
Allowable Entries: Disable = Equipment Mode

Enable = Network Mode

Default Value:

Disable

ALARM ACKNOWLEDGER — This configuration is used

to specify whether the Touch Pilot™ display will act as the

alarm acknowledger for the CCN. There can be only one alarm

acknowledger per CCN. Therefore, if another CCN device

such as ComfortVIEW™ software, the Autodial Gateway or

TeLINK is already set as the alarm acknowledger for the CCN

network then this decision should be set to No.
NOTE: The display must be in Network mode and connected

to the primary CCN bus and this decision set to Yes for alarm

acknowledgement to be enabled.
Allowable Entries: No

Yes

Default Value:

No

BROADCAST ACKNOWLEDGER — This configuration

is used to indicate whether the Touch Pilot display will act as

the broadcast acknowledger for its CCN bus. There can be only

one broadcast acknowledger per CCN bus.
NOTE: The display must be in Network mode and this deci-

sion set to Yes for broadcast acknowledgement to be enabled.
Allowable Entries: No

Yes

Default Value:

0

EQUIPMENT CCN ADDRESS — When in equipment

mode (USERCONF Table’s Network Mode decision is set to

Disable), the Bus Number and Element Number decisions are

used to specify the CCN address of the piece of equipment to

communicate with. An Attach or power cycle must be

performed for changes to take effect. These decisions will be

ignored when the display is connected to the LEN bus or in

Network mode. In Network mode, specify the bus and element

number of the equipment communicate with using the dis-

play’s Attach function.
NOTE: In Network mode, these configurations will be over-

written with the default device address if it is changed through

the Attach process.
BUS NUMBER — This configuration is used to specify the

Equipment Controller bus number.
Allowable Entries: 0 through 239
Default Value:

0

ELEMENT NUMBER — This configuration is used to speci-

fy the Equipment Controller element number.
Allowable Entries: 1 through 239
Default Value:

1

Machine Control Methods —

Three variables con-

trol how the machine operates. These variables control the

On-Off function, set point operation, and Heat-Cool operation.

Machine On/Off Control —

Machine On/Off control

depends on which interface display is used. The control is dif-

ferent for Touch Pilot™ or Navigator™ displays. Select the

correct configuration procedure below based on which inter-

face is being used.
TOUCH PILOT MACHINE CONTROL — Machine On/Off

control is determined locally by pushing the Start/Stop button

on the Touch Pilot display. Pressing this button will cause the

Equipment Start screen to be displayed. See Fig. 15.

Fig. 15 — Equipment Start Screen

Advertising