To configure this option with the Navigator display:

In the following example, a 4 mA signal is Demand Limit

for compressor current is 2000 amps and a 20 mA Demand

Limit signal corresponds with a compressor current of 0 amps.

The 4 to 20 mA signal is connected to TB6-1 and TB6-2. The

demand limit is a linear interpolation between the two values

entered. If the machine receives a 12 mA signal, the machine

controls will limit the total compressor current capacity to

1000 amps. See Fig. 25.
CCN LOADSHED CONTROLLED DEMAND LIMIT —

To configure Demand Limit for CCN Loadshed control, the

unit Operating Type Control must be in CCN control. With the

Touch Pilot™ display, the machine must be started with CCN

Control. For the Navigator™ display, the Operating Control

Type (I/O Button, OPER) must be CCN CONTROL.

The unit must be controlled by a Chillervisor module. The

Chillervisor module can force the demand limit variable and

directly control the capacity of the machine. Additionally, the

unit’s set point will be artificially lowered to force the chiller to

load to the demand limit value.

Ice Storage Operation —

Chiller operation can be

configured to make and store ice. The energy management

module and an Ice Done Switch are required for operation in

the Ice Mode. In this configuration, the machine can operate

with up to three cooling set points: Cooling Set Point 1 (Cool-

ing Setpoint 1, CSP.1) is used during the Occupied period;

Cooling Set Point 2 (Cooling Setpoint 2, CSP.2) is used dur-

ing the Unoccupied period when the ice build is complete (Ice

Done Switch is closed); and Cooling Ice Set Point (Cooling

Ice Setpoint, CSP.3) is used during the unoccupied period

while ice is building (Ice Done Switch is open).

To configure this option with the Touch Pilot display:

To configure this option with the Navigator display:

A power cycle is required for the values to take effect.

Broadcast Configuration —

The 30XW chiller is ca-

pable of broadcasting time, date, and holiday status to all ele-

ments in the CCN system. In the stand-alone mode, broadcast

must be activated to utilize holiday schedules and adjust for

daylight saving time. If the chiller is to be connected to a CCN

system, determine which system element is to be the network

broadcaster to all other system elements. Broadcast is activated

and deactivated in the BRODEFS Table. It is accessible from

Touch Pilot display (Config BRODEFS) or through Network

Service Tool. It is not accessible through Navigator display.

Only one element should be configured as a broadcaster. If

a broadcast is activated by a device that has been designated as

a network broadcaster, then broadcasted time, date, and holiday

status will be updated over the CCN system. If broadcast is en-

abled, a broadcast acknowledger must also be enabled. The ac-

knowledger cannot be the same machine as the broadcasting

machine.
ACTIVATE — The Activate variable enables the broadcast

function of the ComfortLink controls. If this variable is set to 0,

this function is not used and holiday schedules and daylight

savings compensation are not possible. Setting this variable to

1 allows the machine to broadcast and receive broadcasts on

the network. The following information is broadcast: the time

with compensation for daylight savings, date, and holiday flag.

ITEM

ITEM EXPANSION

PATH

VALUE

DMDC

Demand Limit
Select

Configuration

RSET

4-20MA INPUT
Default =
NONE

DMMX

mA for 100%
Demand Lim

Configuration

RSET

Default =
0.0 mA

DMZE

mA for 0%
Demand Limit

Configuration

RSET

Default =
10.0 mA

CUR.S

Current Limit
Select

Configuration

OPTN

YES
Default: NO

CUR.F

Current Limit
at 100%

Configuration

OPTN

Default =
2000

DISPLAY NAME

PATH

LINE NO.

VALUE

Ice Mode Enable

Config

USER

42

Yes

ITEM

ITEM EXPANSION

PATH

VALUE

ICE.M

Ice Mode Enable

Configuration

OPTN

ENBL

0

10

20

30

40

50

60

70

80

90

100

12

14

16

18

20

mA Demand Limit Signal

% Demand Limit

mA For 0% Demand Limit,

DMZE

mA For 100% Demand Limit,

DMMX

0

2

4

6

8

10

Fig. 24 — 4 to 20 mA Demand Limit (Capacity)