APPENDIX C — CCN TABLES (cont)

STATUS DISPLAY TABLES (cont)

*Not supported.

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

RECLAIM*

Heat Reclaim Select

Yes/no

RECL_SEL

Reclaim Condenser Pump

On/Off

CONDPUMP

Reclaim Condenser Flow

On/Off

CONDFLOW

Reclaim Condenser Heater

On/Off

cond_htr

Reclaim Entering Fluid

±nnn.n

°F

HR_EWT

Reclaim Leaving Fluid

±nnn.n

°F

HR_LWT

Reclaim Fluid Setpoint

±nnn.n

°F

RSP

forcible

Reclaim Valve Position

±nnn.n

%

hr_v_pos

HEAT RECLAIM CIRCUIT A
Reclaim Status Circuit A

n

hrstat_a

Pumpdown Pressure Cir A

±nnn.n

psi

PD_P_A

Sub Condenser Temp Cir A

±nnn.n

°F

hr_subta

Pumpdown Saturated Tmp A

±nnn.n

°F

hr_sat_a

Subcooling Temperature A

±nnn.n

^F

hr_subca

Air Cond Entering Valv A

On/Off

hr_ea_a

Water Cond Enter Valve A

On/Off

hr_ew_a

Air Cond Leaving Valve A

On/Off

hr_la_a

Water Cond Leaving Val A

On/Off

hr_lw_a

HEAT RECLAIM CIRCUIT B
Reclaim Status Circuit B

n

hrstat_b

Pumpdown Pressure Cir B

±nnn.n

psi

PD_P_B

Sub Condenser Temp Cir B

±nnn.n

°F

hr_subtb

Pumpdown Saturated Tmp B

±nnn.n

°F

hr_sat_b

Subcooling Temperature B

±nnn.n

^F

hr_subcb

Air Cond Entering Valv B

On/Off

hr_ea_b

Water Cond Enter Valve B

On/Off

hr_ew_b

Air Cond Leaving Valve B

On/Off

hr_la_b

Water Cond Leaving Val B

On/Off

hr_lw_b

STATEGEN

UNIT DISCRETE IN
On/Off – Remote Switch

Open/Clse

ONOFF_SW

Remote Heat/Cool Switch

Open/Clse

HC_SW

Current Control

Off, On Cool, On Heat,
On Auto

on_ctrl

Remote Reclaim Switch

Open/Clse

RECL_SW

Free Cooling Disable Switch*

Open/Clse

FC_SW

Remote Setpoint Switch

Open/Clse

SETP_SW

Limit Switch 1 Status

Open/Clse

LIM_SW1

Limit Switch 2 Status

Open/Clse

LIM_SW2

Occupied Override Switch

Open/Clse

OCC_OVSW

Ice Done Storage Switch

Open/Clse

ICE_SW

Cooler Flow Switch

Open/Clse

FLOW_SW

Cooler Pump Run Status

Open/Clse

CPUMPDEF

Condenser Flow Status

On/Off

CONDFLOW

Remote Interlock Status

Open/Clse

REM_ LOCK

Electrical Box Interlock*

Open/Clse

ELEC_BOX

UNIT DISCRETE OUT
Cooler Flow Setpoint Out*

On/Off

SET_FLOW

Electrical Heat Stage*

0-4/Off

EHS_STEP

Cooler Pump #1 Command

On/Off

CPUMP_1

forcible

Cooler Pump #2 Command

On/Off

CPUMP_2

forcible

Rotate Cooler Pumps ?

Yes/No

ROTCPUMP

forcible

Condenser Pump #1 Out

On/Off

HPUMP_1

forcible

Condenser Pump #2 Out*

On/Off

HPUMP_2

forcible

Rotate Condenser Pumps?*

Yes/No

ROTHPUMP

forcible

Cooler Heater Command*

On/Off

COOLHEAT

Shutdown Indicator State

On/Off

SHUTDOWN

Alarm Relay Status

On/Off

ALARMOUT

Alert Relay Status

On/Off

ALERT

Ready or Running Status*

On/Off

READY

Running Status

On/Off

RUNNING

UNIT ANALOG
Cooler Entering Fluid

±nnn.n

°F

COOL_EWT

Cooler Leaving Fluid

±nnn.n

°F

COOL_LWT

Condenser Entering Fluid

±nnn.n

°F

COND_EWT

Condenser Leaving Fluid

±nnn.n

°F

COND_LWT

Cooler Heater Temp*

±nnn.n

°F

HEATER

Circuit C Heater Temp*

±nnn.n

°F

T_HEAT_C

Optional Space Temp

±nnn.n

°F

SPACETMP

CHWS Temperature

±nnn.n

°F

CHWSTEMP

Reset /Setpnt 4-20mA Sgnl

±nn.n

ma

SP_RESET

Limit 4-20mA Signal

±nn.n

ma

LIM_ANAL

Chiller Capacity Signal

±nn.n

volts

CAPT_010

STRTHOUR

Machine Operating Hours

nnnnn

hours

HR_MACH

Machine Starts Number

nnnnn

st_mach

Compressor A Hours

nnnnn

hours

HR_CP_A

Compressor A Starts

nnnnn

st_cp_a

Compressor B Hours

nnnnn

hours

HR_CP_B

Compressor B Starts

nnnnn

st_cp_b

Compressor C Hours

nnnnn

hours

HR_CP_C

Compressor C Starts

nnnnn

st_cp_c

WATER PUMPS
Cooler Pump #1 Hours

nnnnn

hours

hr_cpum1

Cooler Pump #2 Hours

nnnnn

hours

hr_cpum2

Condenser Pump #1 Hours

nnnnn

hours

hr_hpum1

Condenser Pump #2 Hours*

nnnnn

hours

hr_hpum2