APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — SERVICE TEST

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

STATUS

CCN TABLE

CCN POINT

PAGE

NO.

TEST

MANUAL TEST MODE

Remote-Off-
Enable Switch
must be set to
OFF Position

Remote-Off-
Enable Switch
must be set to
ENABLE
Position

N/A

T.REQ

Manual Sequence

OFF/ON

forcible

N/A

service_test

61, 83

CP.A

Compressor A Output

OFF/ON

forcible

N/A

comp_serv_a

64

SLI.A

Slide Valve Capacity A

unchanged
increase
decrease

forcible

comp_ser_sid_a

CP.B

Compressor B Output

OFF/ON

forcible

N/A

comp_serv_b

64

SLI.B

Slide Valve Capacity B

unchanged
increase
decrease

forcible

comp_ser_sid_b

CP.C

Compressor C Output

OFF/ON

forcible

N/A

comp_serv_c

64

SLI.C

Slide Valve Capacity C

unchanged
increase
decrease

forcible

comp_ser_sid_c

QUIC

QUICK TEST MODE

Remote-Off-
Enable Switch
must be set to
OFF Position

N/A

Q.REQ

OFF/ON

forcible

N/A

61

EXV.A

Circuit A EXV % Open

XXX (%)

0-100

forcible

N/A

61

EXV.B

Circuit B EXV % Open

XXX (%)

0-100

forcible

N/A

61

EXV.C

Circuit C EXV % Open

XXX (%)

0-100

forcible

N/A

ECO.A

Circ A ECO EXV %

XXX (%)

0-100

forcible

ECO.B

Circ B ECO EXV %

XXX (%)

0-100

forcible

ECO.C

Circ C ECO EXV %

XXX (%)

0-100

forcible

FAN.A

Circuit A Fan Stages

X

0-8

forcible

N/A

FAN.B

Circuit B Fan Stages

X

0-8

forcible

N/A

FAN.C

Circuit C Fan Stages

X

0-8

forcible

N/A

SPD.A

Cir A Varifan position

XXX (%)

0-100

forcible

N/A

SPD.B

Cir B Varifan position

XXX (%)

0-100

forcible

N/A

SPD.C

Cir C Varifan position

XXX (%)

0-100

forcible

N/A

HT.A

Oil Heater Circuit A

OFF/ON

forcible

SL1.A

Slide Valve 1 Cir A

OFF/ON

forcible

SL2.A

Slide Valve 2 Cir B

OFF/ON

forcible

HGP.A

Hot Gas Bypass A Output

OFF/ON

forcible

OLS.A

Oil Solenoid Cir A

OFF/ON

forcible

DGT.A

DGT Cool Solenoid A

OFF/ON

forcible

HT.B

Oil Heater Circuit B

OFF/ON

forcible

SL1.B

Slide Valve 1 Cir B

OFF/ON

forcible

SL2.B

Slide Valve 2 Cir B

OFF/ON

forcible

HGP.B

Hot Gas Bypass B Output

OFF/ON

forcible

OLS.B

Oil Solenoid Cir A

OFF/ON

forcible

DGT.B

DGT Cool Solenoid B

OFF/ON

forcible

HT.C

Oil Heater Circuit C

OFF/ON

forcible

SL1.C

Slide Valve 1 Cir C

OFF/ON

forcible

SL2.C

Slide Valve 2 Cir C

OFF/ON

forcible

HGP.C

Hot Gas Bypass C Output

OFF/ON

forcible

OLS.C

Oil Solenoid Cir A

OFF/ON

forcible

DGT.C

DGT Cool Solenoid C

OFF/ON

forcible

PMP.1

Water Exchanger Pump 1

OFF/ON

Not supported.

forcible

N/A

PMP.2

Water Exchanger Pump 2

OFF/ON

Not supported.

forcible

N/A

PMP.3

Condenser Pump 1

OFF/ON

Not supported.

forcible

CL.HT

Cooler Heater Output

OFF/ON

N/A

BVL.A

Ball Valve Position A

OPEN/CLSE

BVL.B

Ball Valve Position B

OPEN/CLSE

BVL.C

Ball Valve Position C

OPEN/CLSE

Q.RDY

Chiller Ready Status

OFF/ON

forcible

N/A

Q.RUN

Chiller Running Status

OFF/ON

forcible

N/A

SHUT

Customer Shutdown Stat

OFF/ON

forcible

N/A

CATO

Chiller Capacity in 0-10v

XX.X (vdc)

forcible

N/A

ALRM

Alarm Relay

OFF/ON

forcible

N/A

68

ALRT

Alert Relay

OFF/ON

forcible

N/A