Cooler pump control – Carrier AQUAFORCE 30XW150-400 User Manual

Page 28

Advertising
background image

28

Cooler Pump Control —

It is required for all chillers

that the cooler pump control be utilized unless the chilled water

pump runs continuously or the chilled water system contains a

suitable concentration of antifreeze solution. When the Cooler

Pumps Sequence is configured, the cooler pump output will be

energized when the chiller enters an "ON" mode. The cooler

pump output is also energized when certain alarms are generat-

ed. The cooler pump output should be used as an override to

the external pump control if cooler pump control is not utilized.

The cooler pump output is energized if a P.01 Water Exchanger

Freeze Protection alarm is generated, which provides addition-

al freeze protection if the system is not protected with a suitable

antifreeze solution.

The 30XW units can be configured for external cooler

pump control. Cooler Pumps Sequence is the variable that

must be confirmed in the field. Proper configuration of the

cooler pump control is required to provide reliable chiller oper-

ation. The factory default setting for Cooler Pumps Sequence is

0 (No Pump). The configuration settings for Cooler Pumps Se-

quence are 1 (1 pump only) for single pump control and 2 (2

pumps auto). Configuration settings 3 (PMP 1 Manual) and 4

(PMP 2 Manual) are for dual pump control only.

If the Cooler Pumps Sequence (PUMP) is set to 1, the con-

trol will start the pump. If a flow failure is detected, the unit

will shut down and must be manually reset. If the Cooler

Pumps Sequence (PUMP) is set to 2, the control will start the

lead pump and automatically alternate the operation of the

pumps to even the wear. If a flow failure is detected, the unit

will shut down and the lag pump will attempt to start. If flow is

established within the Unit Off to On Delay (DELY) period the

unit will restart automatically.

Two manual control options are also available. When the

Cooler Pumps Sequence (PUMP) is set to 3, Cooler Pump 1

will always operate. If a flow failure is detected, the unit will

shut down and must be manually reset. When the Cooler

Pumps Sequence (PUMP) is set to 4, Cooler Pump 2 will al-

ways operate. If a flow failure is detected, the unit will shut

down and must be manually reset.

For all Cooler Pumps Sequence (PUMP) settings (including

0), closure of both the chilled water flow switch (CWFS) and

the chilled water pump interlock contact (connected across

TB5 terminals 1 and 2) are required. In addition, for Cooler

Pumps Sequence settings of PUMP = 1, 2, 3, 4, normally open

auxiliary contacts for Pump 1 and Pump 2 (wired in parallel)

must be connected to the violet and pink wires located in the

harness from the MBB-J5C-CH18 connector. The wires in the

harness are marked "PMP1-13" and "PMP1-14". See the field

wiring diagram in the 30XW Installation Instructions.

Regardless of the cooler pump control option selected, if the

chilled water flow switch/interlock does not close within the

Unit Off to On Delay period after the unit is enabled and in an

ON mode, alarm P.91 will be generated. Other conditions

which will trigger this alarm include:
• Cooler pump interlock is open for at least 15 seconds during

chiller operation.

• Lag chiller in Master/Slave Control pump interlock does not

close after 1 minute of the pump start command.

• Cooler pump control is enabled and the chilled water flow

switch/interlock is closed for more than 2 minutes following

a command to shut down the pump.
The last alarm criterion can be disabled. If Flow Checked if

Pmp Off (Configuration OPTN P.LOC) is set to NO, the con-

trol will ignore the pump interlock input if the cooler pump

output is OFF.

The ComfortLink™ controls have the ability to periodically

start the pumps to maintain the bearing lubrication and seal in-

tegrity. If Pump Sticking Protection (Configuration OPTN

PM.PS) is set to YES, and if the unit is off at 2:00 PM, a pump

will be started once each day for 2 seconds. If the unit has

2 pumps, Pump 1 will be started on even days (such as day 2, 4,

or 6 of the month); Pump 2 will be started on odd days. The de-

fault for this option is PM.PS=NO.

The pump will continue to run for 60 seconds after an off

command is issued.
COOLER PUMP CONTROL CONFIGURATIONS
No Pump Control — To configure cooler pump control op-

tions with the Touch Pilot™ display:

To configure cooler pump control options with the Naviga-

tor™ display:

Single Pump Control — To configure cooler pump control

options with the Touch Pilot display:

To configure cooler pump control options with the Naviga-

tor display:

Dual Pump and Manual Control — To configure cooler

pump control options with the Touch Pilot™ display:

To configure cooler pump control options with the Naviga-

tor™ display:

DISPLAY NAME

PATH

LINE

NO.

VALUE

Cooler Pumps
Sequence

Main
Menu

Config

USER

8

0 (No Pump
Control)

ITEM

ITEM EXPANSION

PATH

VALUE

PUMP

Cooler Pumps
Sequence

Configuration

OPTN

No Pump

DISPLAY NAME

PATH

LINE

NO.

VALUE

Cooler Pumps
Sequence

Main
Menu

Config

USER

8

1 (Single
Pump Control)

Pump Sticking
Protection

Main
Menu

Config

USER

15

Default = No
No = Disabled
Yes = Enabled

Flow Checked
if C Pump Off

Main
Menu

Config

USER

17

Default = Yes
No = Disabled
Yes = Enabled

ITEM

ITEM EXPANSION

PATH

VALUE

PUMP

Cooler Pumps
Sequence

Configuration

OPTN

1 Pump Only

PM.PS

Periodic Pump
Start

Configuration

OPTN

Default = No
No = Disabled
Yes = Enabled

P.LOC

Flow Checked
if Pmp Off

Configuration

OPTN

Default = Yes
No = Disabled
Yes = Enabled

DISPLAY NAME

PATH

LINE

NO.

VALUE

Cooler Pumps
Sequence

Main Menu

Config

USER

8

2 (2 Pumps Automatic)
3 (Pump 1 Manual)
4 (Pump 2 Manual)

Pump Auto
Rotation Delay

Main Menu

Config

USER

14

Default = 48 hours

Pump Sticking
Protection

Main Menu

Config

USER

15

Default = No
No = Disabled
Yes = Enabled

Flow Checked
if C Pump Off

Main Menu

Config

USER

17

Default = Yes
No = Disabled
Yes = Enabled

ITEM

ITEM EXPANSION

PATH

VALUE

PUMP

Cooler Pumps
Sequence

Configuration

OPTN

2 Pumps Auto
PMP1 Manual
PMP2 Manual

ROT.P

Pump Rotation
Delay

Configuration

OPTN

Default =
48 hours

PM.PS

Periodic Pump
Start

Configuration

OPTN

Default = No
No = Disabled
Yes = Enabled

P.LOC

Flow Checked
if Pmp Off

Configuration

OPTN

Default = Yes
No = Disabled
Yes = Enabled