APPENDIX C — CCN TABLES (cont)

SERVICE CONFIGURATION TABLES

*Not supported.
†0 = No economizer.
NOTES:

1. Table used to disable compressors for maintenance purposes. The

capacity control will consider that these compressors (once set to YES)
are failed manually (no alarm will appear).

2. Enter unit size. This item allows the controls to determine capacity of each

compressor and the total number of fans on each circuit based on a com-
pressor arrangement array (can be viewed in table FACTORY2). It is not
necessary to enter compressor capacity and number of fans on each cir-
cuit. See the 30XW Installation Instructions for more information.

3. Number of fans controlled directly by a variable speed fan actuator using

0 to 10 vdc signal. This will enable the controls to determine the remaining
discrete fan staging outputs from the total fans on each circuit.

4. Used for extra functions with the purpose of energy management such as

occupancy override switch, ice storage, setpoint reset, and demand limit.

5. Compressor capacity will be automatically determined if unit size entered

in FACTORY table matches the values in the unit compressor configura-
tion table.

6. Total number of fans includes fans controlled by a variable speed fan. This

value will be automatically populated if unit size entered in FACTORY
table matches the values in the unit compressor configuration table.

TABLE

DISPLAY NAME

RANGE

DEFAULT

UNITS

POINT NAME

WRITE

STATUS

TABLE USED FOR DISABLE COMPRESSORS (see notes)

CP_UNABL
(See Notes)

Compressor A Disable

No/Yes

No

un_cp_a

Compressor B Disable

No/Yes

No

un_cp_b

Compressor C Disable

No/Yes

No

un_cp_c

FACTORY
(See Notes)

Unit Type

1 (Cooling Only)
2 (Heat Pump)*
3 (Water Cooled)
4 (Heat Machine)

1

unit_typ

Unit Capacity

0 to 1800

Nominal Unit Size

unitsize

Power Frequence 60HZ Sel

Yes/No

Yes

freq_60H

Power Supply Voltage

200 to 660

460

volts

voltage

NB Fans on Varifan Cir A

0 to 6

1

varfan_a

NB Fans on Varifan Cir B

0 to 6

1

varfan_b

NB Fans on Varifan Cir C

0 to 6

0

varfan_c

Soft Starter Select

Yes/No

No

softstar

Wye Delta Start Select

Yes/No

No

wye_delt

Air Cooled Reclaim Sel

Yes/No

No

recl_opt

Free Cooling Select

Yes/No

No

freecool

Cooler Heater Select

Yes/No

Yes

heat_sel

Condenser Water Val Sel*

Yes/No

No

cond_val

Hot Gas Bypass Select

Yes/No

No

hgbp_sel

MCHX Exchanger Select

Yes/No

Yes

mchx_sel

Boiler Command Select

Yes/No

No

boil_sel

Energy Management Module

Yes/No

No

emm_nrcp

High Tiers Display Selec

No = Use Navigator™
display as user interface
(factory installed)
Yes = Use Touch Pilot™
Display as user interface
(factory installed)

No

highdisp

Factory Password

0 to 9999

111

fac_pass

Hydraulic Transducer Kit

Yes/No

No

kithydro

Cooler Pass Number

1 to 3

2

cpass_nb

VLT Fan Drive Select*

0

vlt_sel

VLT Fan Drive rpm*

0

vlt_rpm

High Condensing Select

Yes/No

No

highcond

Max Condenser LWT=45degC

Yes/No

No

max_clwt

FACTORY2

Compressor A Config

Must Trip Amps

0 to 600

Refer to Appendix D

cpa_mtac

S1 Config Switch (8 to 1)

00000000 (8 position dip
switch configuration)

Refer to Appendix D

cpa_s1_c

Compressor B Config

Must Trip Amps

0 to 600

Refer to Appendix D

cpb_mtac

S1 Config Switch (8 to 1)

00000000 (8 position dip
switch configuration)

Refer to Appendix D

cpb_s1_c

Compressor C Config

Must Trip Amps

0 to 600

0

cpc_mtac

S1 Config Switch (8 to 1)

00000000 (8 position dip
switch configuration)

0

cpc_s1_c

Circuit A Total Fans NB

2 to 8

0

nb_fan_a

Circuit B Total Fans NB

2 to 8

0

nb_fan_b

Circuit C Total Fans NB

0 to 8

0

nb_fan_c

EXV A Maximum Steps Numb

0/15000

4260

exva_max

EXV B Maximum Steps Numb

0/15000

4260

exvb_max

EXV C Maximum Steps Numb

0/15000

0

exvc_max

Economizer A Steps Numb

0/15000

2785†

eco_cnfa

Economizer B Steps Numb

0/15000

2785†

eco_cnfb

Economizer C Steps Numb

0/15000

0

eco_cnfc