process applications. Refer to application information in Prod-

uct Data literature for details.
FLOW RATE REQUIREMENTS — Standard chillers should

be applied with nominal flow rates within those listed in the

Evaporator and Condenser Flow Rates table. Higher or lower

flow rates are permissible to obtain lower or higher tempera-

ture rises. Minimum flow rates must be exceeded to assure

turbulent flow and proper heat transfer in the cooler. See Table

36. See Fig. 27-37 for cooler pressure drop curves.

Consult application data section in the Product Data

literature and job design requirements to determine flow rate

requirements for a particular installation.

Table 36 — Evaporator and Condenser Flow Rates

*Maximum condenser fluid temperature shown for standard condensing
option. High condensing or heat machine option may have leaving fluid tem-
peratures up to 140 F (60 C) and entering up to 128 F (53.3 C).

CAUTION

Operation below minimum flow rate could generate

alarms, which could result in damage to the cooler.

30XW UNIT

EVAPORATOR

CONDENSER

NOMINAL

Leaving Fluid/Entering Fluid

Leaving Fluid/Entering Fluid

Evaporator

Condenser

Minimum

Maximum

Minimum

Maximum*

40 F (4.4 C)/

45 F (7.2 C)

60 F (15.6 C)/

70 F (21.1 C)

70 F (21.1 C)/

65 F (18.3 C)

118 F (47.8 C)/

110 F (43.3 C)

Minimum

Flow Rate

Maximum

Flow Rate

Minimum

Flow Rate

Maximum

Flow Rate

Nominal

Flow Rate

Nominal

Flow Rate

GPM

L/s

GPM

L/s

GPM

L/s

GPM

L/s

GPM

L/s

GPM

L/s

150

Two pass

200

12.6

720

45.4

240

15.1

960

60.6

384

24.2

480

30.3

One pass

384

24.2

1520

95.9

480

30.3

1600

100.9

384

24.2

480

30.3

Three pass

120

7.6

480

30.3

384

24.2

175

Two pass

213

13.4

765

48.3

255

16.1

1020

64.4

408

25.7

510

32.2

One pass

408

25.7

1615

101.9

510

32.2

1700

107.3

408

25.7

510

32.2

Three pass

128

8.0

510

32.2

408

25.7

200

Two pass

241

15.2

869

54.8

290

18.3

1158

731.0

463

29.2

579

36.5

One pass

463

29.2

1834

115.7

579

36.5

1930

121.8

463

29.2

579

36.5

Three pass

145

9.1

579

36.5

463

29.2

325

Two pass

403

25.4

1149

91.4

483

30.5

1932

121.9

773

48.8

966

60.9

One pass

773

48.8

3059

193.0

966

60.9

3220

203.2

773

48.8

966

60.9

Three pass

242

15.2

966

60.9

773

48.8

350

Two pass

429

27.0

1544

97.4

515

32.5

2058

129.8

823

51.9

1029

64.9

One pass

823

51.9

3259

205.6

1029

64.9

3430

216.4

823

51.9

1029

64.9

Three pass

257

16.2

1029

64.9

823

51.9

400

Two pass

481

30.4

1733

109.3

578

36.4

2310

145.7

924

58.3

1155

72.9

One pass

924

58.3

3658

230.8

1155

72.9

3850

242.9

924

58.3

1155

72.9

Three pass

289

18.2

1155

72.9

924

58.3

Fig. 27 — 30XW150-200 Evaporator Marine Waterbox

0.00

5.00

10.00

15.00

20.00

25.00

30.00

35.00

40.00

(0)

(14.9)

(29.8)

(44.8)

(59.7)

(74.6)

(89.5)

(104.4)

(119.4)

ft wg

(kPa)

0

500

1000

1500

2000

gpm

(0)

(31.5)

(63.1)

(94.6)

(126.2) (L/s)

Evaporator Flow Rate

Pressure Drop

3 pass

2 pass

1 pass

a30-4833

NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over
the entire range of evaporator water flow rates represented.