STARTUP DELAY IN EFFECT — This mode is checked

for when the unit is started. This mode is active when the Min-

utes Off Time (Unit Off to On Delay, DELY) timer is active.

The unit will not start until the timer has expired. The mode

will terminate when the timer expires.
SECOND SETPOINT IN USE — This mode is checked for

when the unit is ON. The mode is active when Cooling Set-

point 2 (Cooling Setpoint 2, CSP.2) or Ice Setpoint (Cooling

Ice Setpoint, CSP.3) is in use. While in this mode, the Active

Setpoint (Current Setpoint, SETP) will show the CSP.2 or

CSP.3 value.

While in this mode, the unit will operate to the Cooling Set-

point 2 (CSP.2) or Ice Setpoint (CSP.3). The mode will termi-

nate when the Cooling Setpoint 2 (CSP.2) or Ice Setpoint

(CSP.3) is no longer in use.
RESET IN EFFECT — This mode is checked for when the

unit is ON. The mode will be active when Temperature Reset

(Cooling Reset Select, CRST) is enabled either by CRST=1

(Outside Air Temperature), CRST=2 (Return Water), CRST=3

(4-20 mA Input), or CRST=4 (Space Temperature) and reset is

active.

While in this mode, the Active Setpoint (Current Setpoint,

SETP) will be modified according to the programmed infor-

mation and will be displayed as the Control Point (Control

Point, CTPT). The mode will terminate when the Temperature

Reset is not modifying the active leaving water set point, caus-

ing SETP to be the same as CTPT.
DEMAND LIMIT ACTIVE — This mode is checked for

when the unit is ON. The mode is active when Demand Limit

(Demand Limit Type Select, DMDC) is enabled either by

DMDC=1 (Switch), DMDC=2 (4-20 mA Input), or the Night

Time Low Sound Capacity Limit (Capacity Limit, LS.LT).

The Active Demand Limit Value (Active Demand Limit

Val, LIM) will display the current demand limit according to

the programmed information and the unit’s capacity will be re-

duced to the amount shown or lower. The mode will terminate

when the Demand Limit command has been removed.
RAMP LOADING ACTIVE — This mode is checked for

when the unit is ON. The mode is active when Ramp Loading

(Ramp Loading Select, RL.S) is enabled and the following

conditions are met:

1. The leaving water temperature is more than 4° F (2.2° C)

from the Control Point (Control Point, CTPT), and

2. The rate of change of the leaving water temperature is

greater than the Cool Ramp Loading (Cooling Ramp

Loading, CRMP).

The control will limit the percent capacity increase until one

of the two conditions above are no longer met, then the mode

will terminate.
COOLER PUMPS ROTATION — This mode is checked for

whether the unit is ON or OFF. The mode is active when the

Cooler Pump Sequence (Cooler Pump Run Status,

PUMP=2) (2 Pumps Automatic Changeover) and the Pump

Rotation Delta Timer (Pump Auto Rotation Delay, ROT.P)

have expired.

The control will switch the operation of the pumps. The

lead pump will operate normally. The lag pump will be started,

becoming the lead, and then the original lead pump will be shut

down. This mode will terminate when the pump operation has

been completed.
PUMP PERIODIC START — This mode is active when the

cooler pump is started due to the Periodic Pump Start configu-

ration (Pump Sticking Protection, PM.PS=YES). If the pump

has not run that day, a pump will be started and will run for 2

seconds at 2:00 PM. If the machine is equipped with dual

pumps, Pump no. 1 will run on even days (such as day 2, 4, 6

of the month). Pump no. 2 will run on odd days (such as day 1,

3, 5 of the month). The mode will terminate when the pump

shuts down.
SYSTEM MANAGER ACTIVE — This mode is checked

when the unit is ON or OFF. This mode is active if a System

Manager such as Building Supervisor, Chillervisor System

Manager, or another CCN device is controlling the machine.

When this mode is active, the machine will respond to the

specific commands received from the System Manager. The

mode will be terminated if the System Manager control is

released.
MASTER SLAVE CONTROL ACTIVE — This mode is

checked for if the machine is ON. This mode is active if Master

Slave Control has been enabled. This occurs when two ma-

chines are programmed, one as the master (Master/Slave Se-

lect, MSSL=1 [Master]) and the other as a slave (Master/

Slave Select, MSSL=2 [Slave]).

Both the master and slave machines will respond to the ca-

pacity control commands issued by the master controller. This

may include control point changes and demand limit com-

mands. This mode will terminate when Master Slave Control

has been disabled.
AUTO

CHANGEOVER

ACTIVE

This mode is not

supported.
FREE COOLING ACTIVE — This mode is not supported.
RECLAIM ACTIVE — This mode is not supported.
ELECTRIC HEAT ACTIVE — This mode is not supported.
HEATING LOW EWT LOCKOUT — This mode is not

supported.
CONDENSER PUMPS ROTATION — This

mode

is

checked for whether the unit is ON or OFF. The mode is active

when the condenser pump sequence (Condenser Pump

Sequence, HPUM = Yes) and the pump rotation delta timer

(Pump Auto Rotation Delay, ROT.P) have expired.
ICE MODE IN EFFECT — This mode is checked for when

the unit is ON. This mode is active when Ice Setpoint (Cooling

Ice Setpoint, CSP.3) is in use. While in this mode, the Active

Setpoint (Current Setpoint, SETP) will show the Cooling Ice

Setpoint, CSP.3 value and the unit will operate to the Ice Set-

point (CSP.3). This mode will terminate when the Ice Setpoint

(CSP.3) is no longer in use.
DEFROST ACTIVE ON CIR A — This mode is not supported.
DEFROST ACTIVE ON CIR B — This mode is not supported.
LOW SUCTION CIRCUIT A

LOW SUCTION CIRCUIT B

These modes are checked when the circuit is ON. The

appropriate circuit mode will be active if one of the follow-

ing conditions is true:

1. If the circuit’s saturated suction temperature (SST) is

more than 6° F (3.3° C) less than the freeze point and

both the cooler approach (Leaving Water Temperature –

SST) and superheat (Suction Gas Temperature – SST) are

greater than 15° F (8.3° C).

2. If the circuit is ON and the circuit’s SST is more than

18º F (10.0º C) below the freeze point for more than

90 seconds.

3. If the circuit’s saturated suction temperature is more

than 6° F (3.3° C) below the freeze point for more than

3 minutes.

For a fresh water system (Cooler Fluid Type, FLUD =1),

the freeze point is 34° F (1.1° C). For medium temperature

brine systems, (Cooler Fluid Type, FLUD=2), the freeze point

is Brine Freeze Set Point (Brine Freeze Setpoint, LOSP).

For criterion 1, no additional capacity will be added. For cri-

teria 2 and 3 capacity will be decreased on the circuit. The

mode will terminate when the circuit’s SST is greater than the

freeze point minus 6° F (3.3° C) or the circuit has alarmed.