INSPECTING/CLEANING HEAT EXCHANGERS — In-

spect and clean cooler tubes at the end of the first operating

season. Because these tubes have internal ridges, a rotary-type

tube cleaning system is necessary to fully clean the tubes. Tube

condition in the cooler will determine the scheduled frequency

for cleaning, and will indicate whether water treatment is

adequate in the chilled water/brine circuit. Inspect the entering

and leaving water thermistor wells for signs of corrosion or

scale. Replace the well if corroded or remove any scale if

found.

WATER TREATMENT — Untreated or improperly treated

water may result in corrosion, scaling, erosion or algae. The

services of a qualified water treatment specialist should be

obtained to develop and monitor a treatment program.

CHILLED WATER FLOW SWITCH — A factory-installed

flow switch is installed in the entering water nozzle for all ma-

chines. See Fig. 50 and 51. This is a thermal-dispersion flow

switch. Figure 50 shows typical installation. If nuisance trips of

the sensor are occurring, follow the steps below to correct:

When power is supplied to the device, a warm-up period is

initiated. The warm-up period may take up to 30 seconds.

When enough flow is detected, the switch contacts will close.

The switch closure does not indicate minimum flow require-

ments have been met for the machine.

1. Check to confirm that all strainers are clean, valves are

open and pumps are running. For the case of variable

frequency drive (VFD) controlled pumps, ensure the

minimum speed setting has not been changed.

2. Measure the pressure drop across the cooler (evaporator).

Use the cooler pressure drop curves in Fig. 27-37 to cal-

culate the flow and compare this to system requirements.

3. If the contacts do not close with sufficient flow, then

check the wiring connection to the MBB. If the input sig-

nal is not closed, then the switch needs to be replaced.

CAUTION

Hard scale may require chemical treatment for its preven-

tion or removal. Consult a water treatment specialist for

proper treatment procedures.

CAUTION

Water must be within design flow limits, clean and treated

to ensure proper machine performance and reduce the

potential of tubing damage due to corrosion, scaling, and

algae. Carrier assumes no responsibility for cooler damage

resulting from untreated or improperly treated water.

Fig. 51 — Flow Switch (Typical)

LEGEND

CEWT — Condenser Entering Water Thermistor
CLWT — Condenser Leaving Water Thermistor
CWFS — Chilled Water Flow Switch
EWT

Entering Water Thermistor

LWT

Leaving Water Thermistor

OUT

OUT

IN

IN

LWT

EWT

CLWT

CWFS

CEWT

A30-4846

Fig. 49 — Cooler Head Recommended

Bolt Torque Sequence

1

20

8

6

19

16

15

3

23

10

12

24

14

13

17

5

7

18

2

4

21

9

11

22

A30-4845

Fig. 50 — Chilled Water Flow Switch

WIRING

a30-4708

Advertising