APPENDIX C — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
*Not supported.
†The forced value will be used.
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
GENUNIT
Operating Type
Control Type
L-Off-Local Off
(ComfortLink Controls= On/Off Switch=Opened)
L-On-Local On
L-Sched-Local On/Off State based on Time Schedules
CCN-Unit is in CCN Control
Remote-On/Off Based on Remote Contact
(not applied to ComfortLink Display)
Master-Unit Operation in Lead/Lag and it is a Master
Local
CCN
Remote
OPER_TYP
ctr_type
Run Status
0 = Off
1 = Running
2 = Stopping
3 = Delay
4 = Tripout
5 = Ready
6 = Override
7 = Defrost
8 = Run Test
9 = Test
STATUS
CCN Chiller Start/Stop
Enable/Disable
CHIL_S_S
forcible
Chiller Occupied?
Yes/No
CHIL_OCC
forcible
Minutes Left for Start
0-15
min
min_left
Heat/Cool Status
0 = Cool
1 = Heat
2 = Stand-by
3 = Both
HEATCOOL
Heat/Cool Select
0 = Cool
1 = Heat
2 = Auto
HC_SEL
forcible
Heat Reclaim Select
Free Cooling Selct
Yes/No
Yes/No
RECL_SEL
FC_DSBLE
forcible*
forcible
Alarm State
0 = Normal
1 = Partial
2 = Shutdown
ALM
Current Alarm 1
nnnnn
alarm_1
Current Alarm 2
nnnnn
alarm_2
Current Alarm 3
nnnnn
alarm_3
Current Alarm 4
nnnnn
alarm_4
Current Alarm 5
nnnnn
alarm_5
Percent Total Capacity
nnn
%
CAP_T
Active Demand Limit Val
nnn
%
DEM_LIM
forcible*
Lag Capacity Limit Value
nnn
%
LAG_LIM
Actual Chiller Current
nnn
amps
TOT_CURR
forcible†
Chiller Current Limit
nnn
amps
CURR_LIM
forcible
Current Setpoint
±nnn.n
°F
SP
Setpoint Occupied?
Yes/No
SP_OCC
forcible
Setpoint Control
Setpt 1
Setpt 2
Ice_sp
4-20mA
Auto
sp_ctrl
Control Point
±nnn.n
°F
CTRL_PNT
forcible*
Controlled Water Temp
±nnn.n
°F
CTRL_WT
External Temperature
±nnn.n
°F
OAT
Emergency Stop
Enable/Disable
EMSTOP
forcible
MODES
Startup Delay in Effect
Yes/No
—
Mode_01
Second Setpoint in Use
Yes/No
—
Mode_02
Reset in Effect
Yes/No
—
Mode_03
Demand Limit Active
Yes/No
—
Mode_04
Ramp Loading Active
Yes/No
—
Mode_05
Cooler Heater Active
Yes/No
—
Mode_06
Cooler Pumps Rotation
Yes/No
—
Mode_07
Pump Periodic Start
Yes/No
—
Mode_08
Night Low Noise Active
Yes/No
—
Mode_09
System Manager Active
Yes/No
—
Mode_10
Master Slave Active
Yes/No
—
Mode_11
Auto Changeover Active
Yes/No
—
Mode_12
Free Cooling Active
Yes/No
—
Mode_13
Reclaim Active
Yes/No
—
Mode_14
Electric Heat Active
Yes/No
—
Mode_15
Heating Low EWT Lockout
Yes/No
—
Mode_16
Condenser Pumps Rotation
Yes/No
—
Mode_17
Ice Mode in Effect
Yes/No
—
Mode_18
Defrost Active On Cir A
Yes/No
—
Mode_19
Defrost Active On Cir B
Yes/No
—
Mode_20
Low Suction Circuit A
Yes/No
—
Mode_21
Low Suction Circuit B
Yes/No
—
Mode_22
Low Suction Circuit C
Yes/No
—
Mode_23
High DGT Circuit A
Yes/No
—
Mode_24
High DGT Circuit B
Yes/No
—
Mode_25
High DGT Circuit C
Yes/No
—
Mode_26
High Pres Override Cir A
Yes/No
—
Mode_27
High Pres Override Cir B
Yes/No
—
Mode_28
High Pres Override Cir C
Yes/No
—
Mode_29
Low Superheat Circuit A
Yes/No
—
Mode_30
Low Superheat Circuit B
Yes/No
—
Mode_31
Low Superheat Circuit C
Yes/No
—
Mode_32