Table 24 — Dual Master Chiller Control Parameters for Parallel Applications with Touch Pilot™ Display

DISPLAY NAME

PATH

LINE NO.

VALUE

Master/Slave Select

Main Menu

Config

MST_SLV

3

1 (Master)
Default: 0 (Disable)

Master Control Type

Main Menu

Config

MST_SLV

7

1=Local Control
2=Remote Control
3=CCN Control
Default: 1
Configure for proper control type.

Slave Address

Main Menu

Config

MST_SLV

11

Must be set to the Slave Chiller’s address.
The master and slave chiller must have
different addresses and be on the same
Bus Number
Default: 2

Lead Lag Select

Main Menu

Config

MST_SLV

12

0 (Master Always Leads)
1 (Lag Once Failed Only)
2 (Lead/Lag Runtime Select)
Default: 0 (Master Always Leads)

Lead/Lag Balance Delta

Main Menu

Config

MST_SLV

16

Range: 40 to 400 hours
Default: 168 hours

Lag Start Timer

Main Menu

Config

MST_SLV

17

Range: 2 to 30 minutes
Default: 10 minutes

Lead Pulldown Time

Main Menu

Config

MST_SLV

18

Range: 0 to 60 minutes
Default: 0 minutes

Start If Error Higher

Main Menu

Config

MST_SLV

19

Range: 3.0 to 18

F (1.7 to 10.0 C)

Default: 4.0

F (2.2 C)

Lag Minimum Running Time

Main Menu

Config

MST_SLV

20

Range: 0 to 150 minutes
Default: 0 minutes

Lag Unit Pump Control

Main Menu

Config

MST_SLV

21

0 (Stop If Unit Stops)
1 (Run If Unit Stops)
Default: 0 (Stop If Unit Stops)

Chiller In Series

Main Menu

Config

MST_SLV

22

Default: No
Value: No