Carrier AQUAFORCE 30XW150-400 User Manual

Page 67

Advertising
background image

67

Refrigerant Circuit

LEAK TESTING — Units are shipped with complete operat-

ing charge of refrigerant R-134a or nitrogen (see Physical Data

tables supplied in the 30XW installation instructions) and

should be under sufficient pressure to conduct a leak test. If

there is no pressure in the system, introduce enough nitrogen to

search for the leak. Repair the leak using good refrigeration

practices. After leaks are repaired, system must be evacuated

and dehydrated.
REFRIGERANT CHARGE — Refer to Physical Data tables

supplied in the 30XW installation instructions. Immediately

ahead of filter drier in each circuit is a factory-installed liquid

line service valve. Each valve has a

1

/

4

-in. access connection

for charging liquid refrigerant.
Charging with Unit Off and Evacuated — Close liquid line

service valve before charging. Weigh in charge shown on unit

nameplate. Open liquid line service valve; start unit and allow

it to run several minutes fully loaded. Check for a clear sight

glass. Be sure clear condition is liquid and not vapor.
Charging with Unit Running — If charge is to be added while

unit is operating, loop water temperatures should be near the

ARI rating point (54/44 F evaporator; 85/95 F condenser). At

these conditions and with the circuit at full load, charge to a

clear sightglass and a liquid line temperature of 90 to 93 F (32.2

to 33.9 C).

Add 5 lb (2.3 kg) of liquid charge into the fitting located on

the tube entering the bottom of the cooler. This fitting is located

between the electronic expansion valve (EXV) and the cooler.

Allow the system to stabilize and then recheck the liquid

temperature. If needed, add additional liquid charge, 5 lb

(2.3 kg) at a time, allowing the system to stabilize between

each charge addition. Slowly add charge as the sight glass

begins to clear to avoid overcharging.

Safety Devices —

The 30XW chillers contain many

safety devices and protection logic built into the electronic

control. Following is a description of the major safeties.
COMPRESSOR PROTECTION
Motor Overload — The compressor protection modules

(CPM) protect each compressor against overcurrent. Do not

bypass the current transducers or make any changes to the

factory-installed and configured headers. The configuration of

these headers defines the Must Trip Amps (MTA) at which the

CPM will turn the compressors off. Determine the cause for

trouble and correct the problem before resetting the CPM. See

Appendix D for MTA settings and configuration headers.

Each CPM board also reads the status of each compressor’s

high-pressure switch. All compressors have factory-installed

high-pressure switches. See Table 47.

Table 47 — High-Pressure Switch Settings

If the switch opens during operation, the compressor will be

shut down. The CPM will reset automatically when the switch

closes, however, a manual reset of the control is required to

restart the compressor.

COOLER PROTECTION
Low Water Temperature — Microprocessor is programmed

to shut the chiller down if the leaving fluid temperature drops

below 34 F (1.1 C) for water or more than 8

 F (4.4 C) below

set point for Fluid Type = brine. When the fluid temperature

rises 6

 F (3.3 C) above the leaving fluid set point, the safety

resets and the chiller restarts. Reset is automatic as long as this

is the first occurrence of the day.

Relief Devices —

Fusible plugs are located in each cir-

cuit between the condenser and the liquid line shutoff valve.
PRESSURE RELIEF VALVES — Valves are installed in each

circuit and are located on all coolers and condensers. These

valves are designed to relieve if an abnormal pressure condition

arises. Relief valves on all coolers relieve at 220 psi (1517 kPa).

These valves should not be capped. If a valve relieves, it should

be replaced. If the valve is not replaced, it may relieve at a lower

pressure, or leak due to trapped dirt from the system which may

prevent resealing. Valves on standard condensers relieve at

220 psi (1517 kPa). Valves on high condensing and heat reclaim

units relieve at 300 psi (2068 kPa).

Pressure relief valves located on shells have

3

/

4

-in. NPT

connections for relief. Some local building codes require that

relieved gases be exhausted to a specific location. This connec-

tion allows conformance to this requirement. Refer to Installa-

tion Instructions for details.

MAINTENANCE

Recommended Maintenance Schedule —

The fol-

lowing are only recommended guidelines. Jobsite conditions

may dictate that maintenance schedule is performed more often

than recommended.
Every month:

• Check moisture indicating sight glass for possible refriger-

ant loss and presence of moisture.

Every 3 months:

• Check refrigerant charge.

• Check all refrigerant joints and valves for refrigerant leaks;

repair as necessary.

• Check chilled water and condenser flow switch operation.

• Check oil filter pressure drop.

Every 12 months:

• Check all electrical connections; tighten as necessary.

• Inspect all contactors and relays; replace as necessary.

• Check accuracy of thermistors; replace if greater than ±2° F

(1.2° C) variance from calibrated thermometer.

• Check accuracy of transducers; replace if greater than ±5 psi

(34.47 kPa) variance.

• Check to be sure that the proper concentration of antifreeze

is present in the chilled water and condenser loops, if

applicable.

• Verify that the chilled water loop is properly treated.

• Check refrigerant filter driers for excessive pressure drop;

replace as necessary.

• Check chilled water and condenser strainers, clean as

necessary.

• Perform Service Test to confirm operation of all components.

• Check for excessive cooler approach (Leaving Chilled

Water Temperature – Saturated Suction Temperature) which

may indicate fouling. Clean cooler vessel if necessary.

• Obtain oil analysis; change as necessary.

TROUBLESHOOTING

See Table 48 for an abbreviated list of symptoms, possible

causes and possible remedies.

IMPORTANT: When adjusting refrigerant charge, circu-

late fluid through cooler and condenser continuously to

prevent freezing and possible damage to both. Do not

overcharge, and never charge liquid into the low-pressure

side of system.

30XW UNIT

SWITCH SETTING

psig

kPa

STD

217.6 +7.25, –14.5

1500 +50, –100

HIGH COND

304.5 +7.25, –14.5

2099 +50, –100

IMPORTANT: If unit is installed in an area where

ambient temperatures fall below 32 F (0° C), a suit-

able corrosion-inhibited antifreeze solution must be

used in the chilled water and condenser water circuit.

Advertising