6.2
CLAMPING CABLES AND SHIELDING CABLES
Of the cables connected to the YASNAC, clamp those that need shielding to the ground plate
securely with the cable clamping fixtures as shown in the figure below.
This clamping serves
not only as cable support but also as cable shielding.
In ensuring safe operation of the system,
it is extremely important that you clamp the necessary cables without fail.
(a) Strip part of the cable shield as shown in the figure below to expose the shield enclosure.
Press the exposed part onto the ground plate using the cable clamp.
(b) Mount the ground plate near the cable opening.
for non-shielded cables for clamping.
CABLE
TYPE 1
TYPE 2
DF8401485
19.5
URE
I I
‘
0
‘
LAMP
P L A T E
Fig. 6.1
Shielding Cables
16