A6. precautions for application, A6. 1 minus load, A6. 2 load inertia (gd – Yaskawa i80M Connecting Manual User Manual

Page 315: A6. 3 high voltage line

Advertising
background image

A6. PRECAUTIONS FOR APPLICATION

A6. 1 MINUS LOAD

The motor is rotated by the load; it is impossible to apply brake (regenerative brake) against
this rotation and achieve continuous running.

Example Driving a motor to lower objects (with no counterweight)

Since Servopack has the regenerative brake capability of short time (corresponding to the

motor stopping time), for application to a minus load, contact Yaskawa representative.

A6. 2 LOAD INERTIA (GD

2

)

The allowable load inertia GD

2

converted to the motor shaft must be within five times the rotor

inertia (J

M

) of the applicable AC

If the allowable load inertia (J

L

) is exceeded, an

overvoltage alarm may be given during deceleration.

If this occurs, take the following actions:

Reduce the current limit.

Slow down the deceleration curve.

Decrease the maximum speed.

For details, contact Yaskawa representative.

A6. 3 HIGH VOLTAGE LINE

If the supply voltage is 400/440VAC, the voltage must be dropped three-phase, 400/440VAC to

200VAC by using a power transformer.

Table A7. 2 shows the transformer selection. Connec-

tion should be made so that the power is supplied and cut through the primary side of the trans-
former. Single-phase 100VAC class power supply should not be used.

315

Advertising