With an external servo unit, design the the servo control circuit power input sequence so

that the circuit is energized at the output

signals.

(c) Again make the same power switching (depressing the POWER ON button or closing the

circuit between EON and

Now, the servo power supply is turned on, and the out-

put of/SVMX signals (servo power input and output) is activated.

With an external servo unit, design the servo power circuit power input sequence so that

the circuit is energized at the output

signals.

(d) /BK output is turned on by parameters after the servo is ready (in servo clamp condi-

tion). Release the brake unit with this signal.

(e) When the external circuit is ready after the circuit between/SVMX is closed, and the con-

trol becomes ready, close the MRD (machine ready) input of the

module. Then, RDY

is displayed on the CRT, and operation becomes possible.

POWER ON PB
OR EON INPUT
POWER OFF PB
ON EOF INPUT

\

\

* ESP INPUT

\

\

\

I

\

\

\

OUTPUT

I

I

SERVO READY

I

PARAMETER

OUTPUT

pm

pm

I

MRD INPUT

I

I

I

I

ALARM CODE

’2190>

‘3000.

:

RESET KEY

ON

Fig. 10.4 Time Chart of Power Supply Turning on Sequence

3.2 EMERGENCY STOP

ESP) INPUT

When the emergency stop input circuit (* ESP) is open, the control stops totally, the /SVMX and
/BK are turned off, and the emergency stop output (

of general purpose

module is

opened.

10.3.3 EXTERNAL POWER ON- OFF (EON, EOF,

INPUT

The control can be switched on and off by external input signals, in the same way as the de-
pressing of the POWER ON/OFF buttons on the NC operator’s station. When the circuit be-
tween EON and ECOM is closed, the logic circuit or servo power of the control is energized.
When the circuit between EOF and ECOM is opened, the logic circuit or servo power of the

control is deenergized.