Minimum system requirements – Edwards Signaling eFSA250 User Manual

Page 10

Advertising
background image

viii

E-FSA64 and E-FSA250 Technical Reference Manual

Users should ensure for their own protection that the electrical ground

connections of the power utility, telephone lines, and internal metallic water pipe

system, if present, are connected together. This precaution may be particularly

important in rural areas.

Note:

The Load Number (LN) assigned to each terminal device denotes the

percentage of the total load to be connected to a telephone loop that is used by

the device, to prevent overloading. The termination on a loop may consist of any

combination of devices subject only to the requirements that the sum of the Load

Numbers of all the devices does not exceed 100.

Minimum system requirements

The table below lists the minimum hardware requirements for each type of

system for which the control panel is listed.

Table 1: Minimum hardware requirements for applications
System

Equipment needed

Protected Premises (Local) Fire Alarm System Control panel

Appropriately sized batteries

Auxiliary Fire Alarm System, Local Energy Type Control panel

Appropriately sized batteries
CTM module

Remote Supervising Station Fire Alarm System Control panel

Appropriately sized batteries
SA-DACT or RPM module

Central Station Fire Alarm System

Control panel
Appropriately sized batteries
SA-DACT or RPM module

To get started

If you are just starting out, follow the items in this checklist to prepare, install,

wire, and program your fire alarm control panel.
1. Prepare the site. Make sure the installation location is free from construction

dust and debris and extreme temperature ranges and humidity.

2. Unpack the equipment.

Advertising
This manual is related to the following products: