Appendix A: Panel specifications

E-FSA64 and E-FSA250 Technical Reference Manual

209

Loop circuit

Maximum loop resistance: 66 Ω

Maximum loop capacitance: 0.7 µF

Communication line voltage: Maximum 20.6 V peak-to-peak

Operating current (fully loaded loop)

Stand by: 60 mA

Alarm: 125 mA (this does not include two-wire smoke modules)

Circuit current: 0.5 A max.

Style 4, 6, and 7 wiring

Max. resistance between isolators: Limited only by overall wire run

lengths

64 isolators maximum (total both isolator bases and modules)

Batteries

Type: Sealed lead acid

Voltage: 24 VDC

Charging current: 2.47 A max.

Amp hour capacity: 26 Ah

Standby operation:

24 hour or 60 hour

Placement: Up to two 10 Ah batteries will fit in the Edwards Signaling

eFSA64 control panel cabinet and two 18 Ah batteries will fit in the

eFSA250 control panel cabinet. If larger batteries are required, you must

use an Edwards battery cabinet.

SA-DACT dialer

Phone line type: One or two loop-start lines on a public, switched

network

Phone line connector: RJ-31/38X (C31/38X)

Communication formats: Contact ID (SIA DC-05)

Operating current

Standby/Alarm: 41 mA

Max.: 100 mA

FCC registration number: GESAL01BSADACT

Industry Canada Registration number: 3944A-SADACT

Ringer equivalence number: 0.1B

Ground fault

impedance

0 to 5 kΩ

Alarm contact

Form C N.O. 24 VDC at 1 A (resistive load)

Trouble contact

Form C 24 VDC at 1 A (resistive load)

Supervisory contact

Form A N.O. 24 VDC at 1 A (resistive load)

Environmental

Temperature: 0 to 49°C (32 to 120°F)
Relative humidity: 0 to 93% noncondensing

Terminal rating

All terminals rated for 12 to 18 AWG (0.75 to 2.5 mm²)