Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

89

To set the activation count:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number

of the correlation group to be programmed.

(Values range from 001 to 199.)

5. Choose Activation Count and enter the activation

count (values range from 01 to 99).

6. Choose Save.

Advanced Program

Loop Configuration

Loop Configuration

Loop Class

Zone

Correlation Groups

Correlation Groups

Number 001<>

Correlation Group 001

Add/Remove Device

Suite Sig Sil No

Activation Count

Activation Count

Number 01

Save

To copy the members of a correlation group:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3 Choose Loop Configuration.
4. Choose Correlation Groups.
5. Enter the number of the correlation group to be

programmed. (Values range from 001 to 199.)

6. Choose Copy and enter the number of the

correlation group to be copied.

7. Choose Save.

Advanced Program

Loop Configuration

Loop Configuration

Loop Class

Zone

Correlation Groups

Correlation Groups

Number 003<>

Correlation Group 003

Add/Remove Device

Suite Sig Sil No

Activation Count

Copy

Copy

From Group 001<>

Save