Chapter 1: Installation and wiring

E-FSA64 and E-FSA250 Technical Reference Manual

7

Figure 7: Transformer primary and secondary wiring

TB1

EGND

24 VAC

IN

Battery wiring (TB8)

Caution:

Connect and disconnect standby batteries only with the AC power

applied.

The control panel has a 24 VDC rechargeable battery circuit that is capable of

charging up to two 26 Ah sealed lead acid batteries.
The table below lists the batteries that can be installed in the control panel

cabinets. Up to two 11 Ah batteries will fit in the eFSA64 control panel cabinet

and two 18 Ah batteries will fit in the eFSA250 point control panel cabinet. If

larger batteries are required, you must use an approved battery cabinet. To

determine which battery the system requires, use the “Battery calculation

worksheet” on page 212.

Table 3: Batteries for eFSA64 and eFSA250 panels
Model

Manufacturer

Rating

12V4A

GS Battery, Inc.

12 volts, 4.5 Ah

12V6A5

GS Battery, Inc.

12 volts, 7.2 Ah

12V10A

GS Battery, Inc.

12 volts, 11 Ah

12V17A

GS Battery, Inc.

12 volts, 18 Ah

12V24A

GS Battery, Inc.

12 volts, 26 Ah

Advertising