Event programming – Edwards Signaling eFSA250 User Manual

Page 140

Advertising
background image

Chapter 2: Front panel programming

128

E-FSA64 and E-FSA250 Technical Reference Manual

Event programming

Panel event programming

Panel events, such as reset, system startup, and battery low have an event

notification setting for contact ID, dialer, NET, and printer, which controls where

the event is sent when it takes place. Each event has a factory default setting

that can be used with no additional programming.

Table 36: Default panel event settings
Panel event

Printer

Dialer

NET (1-8) CID

Aux. power 1 (disable)

Yes

None

No

n/a

Aux. power 1 (trouble)

Yes

Acct 1

No

312

Aux. power 2 (disable)

Yes

None

No

n/a

Aux. power 2 (trouble)

Yes

Acct 1

No

312

Battery charger (disable)

Yes

None

No

n/a

Battery charger (trouble)

Yes

Acct 1

No

309

Battery low (disable)

Yes

None

No

500

Battery low (trouble)

Yes

Acct 1

No

302

Battery missing (disable)

Yes

None

No

n/a

Battery missing (trouble)

Yes

Acct 1

No

311

Clear history

No

Acct 1

No

621

Common alarm

No

Acct 1

No

110

Common disable

No

Acct 1

No

500

Common monitor

No

None

No

n/a

Common supervisory

No

Acct 1

No

200

Common trouble

No

None

No

n/a

Common trouble for network dialer

Yes

None

No

n/a

Common trouble for telco dialer

No

Acct 1

No

373

Date

No

Acct 1

No

625

Dialer disable/remote disconnect

Yes

Acct 1

No

n/a

Dialer line 1 fault (disable)

Yes

None

No

n/a

Dialer line 1 fault (trouble)

Yes

Acct 1

No

351

Dialer line 2 fault (disable)

Yes

None

No

n/a

Dialer line 2 fault (trouble)

Yes

Acct 1

No

352

Advertising