Chapter 3: System operation

164

E-FSA64 and E-FSA250 Technical Reference Manual

To activate or restore an output device:

1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Activate/Restore.
4. Choose Device.
5. Choose the loop the device is on.

Note:

If the panel only has one loop, the loop

selection screen does not display.

6. Enter the device ID for the device that you want to

activate or restore.

7. Press Enter.
8. Press Cancel to return to the previous menu.

— or —
Press the Menu button to exit menu mode.

Main Menu

Reports

Test

Control

Program

Enter Password

0000

Control

Enable/Disable

Activate/Restore

Activate/Restore

Device

Panel NAC

Device

Loop 01<>

Device Activate<>

001

Device 001

Unlatching latched output devices

Latched outputs are devices that are configured to shut down air handlers and

dampers automatically when an alarm activates, and to keep them shut down

until they are manually unlatched and restored. For this reason, devices

configured as latched output devices must be manually unlatched and then

restored.
When outputs have been latched, the panel generates an “Outputs are latched”

event. The unlatch command affects all latched output devices system-wide. You

can assign the Unlatch Outputs command to a programmable key on the front

panel or to one of the following modules: E-ISO, E-IDC1A, E-IDC1B, or E-IDC2B.

To unlatch latched output devices:

1. Press the Unlatch Outputs button on the control panel (if programmed).

— or —
Press the Unlatch Outputs module button (if programmed).