Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

33

Figure 43: Correlation group operation

Correlation group

Input devices (smoke

detector, pull station) by

themselves or in a zone

Output devices and

NAC devices (strobe,

horn)

Input

device

Zone

input

device

Output

device

NAC

output

device

Activation of an input device in the correlation group

turns on every output device in the correlation group

(links input devices to output devices)

A correlation group can contain any combination of input devices, output devices,

NACs, events, and zones. Input devices, output devices, NACs, events, and

zones can be assigned to more than one correlation group. There are 199

available correlation groups. You can add a forty-character, alphanumeric

description to each correlation group.

Figure 44: Inputs and outputs to correlation groups

Correlation

group 001

Correlation

group 002

Correlation

group 003

Correlation

group 199

Zone, NAC, or

output device

Zone, NAC, or

output device

Zone, NAC, or

output device

Zone, NAC, or

output device

During auto programming the following devices are assigned to correlation group

001:
• All addressable smoke detectors

• All addressable pull stations

• All E-2WIRE modules

• All E-IDC1B (mini modules)

• Any circuit on an E-IDC2B or E-IDC1A configured with the P1 or P2 switch in

position 1 (alarm)