Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

63

Option

Description

Event notification

Configures event reporting for zones, individual devices, or both.
Zone: When a device is a member of a zone, only the zone information is

sent to the LCD, LEDs, printer, and dialer. Device level reporting

configuration is not available.
Zone/device: Zone information is sent to the LCD and LEDs. Device

information is sent to the printer and dialer. Zone/device reporting

locations can be configured through custom programming.
Device: Only device information is reported, no zone information

Label devices

Configures the auto programming sequence to allow you to label devices

using the alphanumeric keypad.
Yes: Enables device labeling
No: Disables device labeling

Label zones

Configures the auto programming sequence to allow you to label zones

using the alphanumeric keypad.
Yes: Enables zone labeling
No: Disables zone labeling

Follow

This option controls the conditions that will activate relay or sounder

detector bases. Select from the following values.
Head: The base is controlled by the detector’s settings.
• The base activates when the detector goes into alarm, unless the

detector is set for alarm verification.

• If the detector is set for alarm verification, the base activates when the

detector goes into alarm verification. It does not restore, however,

until the alarm restores.

• The base does not respond when the detector goes into prealarm no

matter how the detector is configured. Also, the base only follows the

primary element of a dual element detector. Any activation from a

secondary element does not trigger the base.

• Devices with the base set to follow Head cannot be placed in

correlation groups. When a device base is set to follow Head, the

base is removed as an output from any correlation groups to which it

belongs.

Alarm: The base activates its relay when the detector goes into alarm.

The base will not restore until the alarm event has been restored.
Alarm and verify (ALM+VFY): The base activates its relay when the

detector goes into alarm verify and continues when the detector goes into

alarm. The base will not restore until both events have been restored.
Alarm and prealarm (ALM+PALM): The base activates its relay when the

detector goes into prealarm and continues when the detector goes into an

alarm. The base will not restore until both events have been restored.
Riser: The base is triggered individually by the loop controller (sounder