Panel backbox wire routing, Ac power wiring – Edwards Signaling eFSA250 User Manual

Page 17

Advertising
background image

Chapter 1: Installation and wiring

E-FSA64 and E-FSA250 Technical Reference Manual

5

Panel backbox wire routing

Using the diagram below, keep power-limited wiring in the shaded area and

nonpower-limited wiring in the unshaded area at all times.

Figure 4: Panel backbox wire routing

00:00:00 01/01/07

,

[1]

[1] Power-limited only when connected to a power-limited source. If connected to a nonpower-

limited source, all wiring on terminal block TB3 must be NPFPL, NPFPLR, or NPFPLP rated

wire or equivalent, in accordance with the NFPA 70 National Electric Code and routed

separately from all power-limited wiring.

AC power wiring

Circuit specifications

• eFSA64 panel: 120 V, 60 Hz, 1.3 A or 230 V, 50/60 Hz,

0.62 A from dedicated branch supply

• eFSA250 panel: 120 V, 60 Hz, 2.0 A or 230 V, 50/60 Hz,

0.97 A from dedicated branch supply

Advertising
This manual is related to the following products: