Chapter 3: System operation

168

E-FSA64 and E-FSA250 Technical Reference Manual

Activating and restoring gas accelerated

response

Use the Activate Gas Accelerated Response option to turn on the accelerated

response mode. Use the Restore Gas Accelerated Response option to turn off

the accelerated response mode.
Under normal conditions, it takes approximately four minutes at 400 PPM of CO

before a CO detector activates. This mimics the normal absorption rate of CO in

the bloodstream. When testing a CO device, you can put the CO detectors in the

CO accelerated response mode, which shortens the time to activation to be

between four to eight seconds at 400 PPM of CO.
You can activate a gas accelerated response on devices that have a CO sensor.

See Table 9 on page 43. Once activated, the gas accelerated response on that

device remains active for four hours, unless you manually restore it, or the device

returns from a communication fault.

To activate gas accelerated response:

1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Activate/Restore.
4. Choose Gas Accel Response.
5. Select the device that you want to accelerate.
6. Press Enter.
7. Press Cancel to return to the previous menu.

— or —
Press the Menu button to exit menu mode.

Main Menu

Reports

Test

Control

Program

Enter Password

0000

Control

Enable/Disable

Activate/Restore

Activate/Restore

Device

Panel NAC

Sensor Bypass

Gas Accel Response

Device Activate<>

xxx

Loop 1 Device 001