Chapter 3: System operation

E-FSA64 and E-FSA250 Technical Reference Manual

173

To disable or enable a panel event:

1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Enable/Disable.
4. Choose Panel Event.
5. Enter the ID number of the event type to disable or

enable.
See “Event ID numbers and descriptions” on page

154 for event descriptions and the list above for

the events that can be disabled.

6. Press Enter.
7. Press Cancel to return to the previous menu.

— or —
Press the Menu button to exit menu mode.

Main Menu

Reports

Test

Control

Program

Enter Password

0000

Control

Enable/Disable

Activate/Restore

Enable/Disable

Device

Zone

Panel Event

Panel Event Disable<>

034

Event 034

When you disable an event:
• The common Disable LED turns on
• The common Trouble LED flashes and the panel goes into a trouble state
• The common Trouble relay changes state
• The disabled and active points indicators on the LCD increment
• The LCD displays a message indicating that the event is disabled.

Disabling and enabling loop events

Disabling a loop event prevents it from being displayed, printed, or reported off

premises. This is typically done during maintenance. For example, you might

want to disable the Loop 1 unconfigured alarm event, if you are switching out a

detector. Remember to enable the event as soon as you have finished working.
When you disable a loop event:
• The common Disable LED turns on
• The common Trouble LED flashes and the panel goes into a trouble state
• The common Trouble relay changes state