Sa-dact testing – Edwards Signaling eFSA250 User Manual

Page 211

Advertising
background image

Chapter 5: Diagnostics, maintenance, and testing

E-FSA64 and E-FSA250 Technical Reference Manual

199

2. Choose Test Fire.
3. Enter a level one password.
4. Choose the loop the device is on.

Note:

If the panel only has one loop, the loop

selection screen does not display. Go to the next

step.

5. Enter the device number of the device you want to

test fire.

6. Press Enter.
7. Choose Start to start the test.
8. When you have finished, press Reset (or repeat

steps 1 to 7 and choose End) to clear the test

alarms and return the system to normal.

9. Press Cancel to return to the previous menu.

— or —
Press the Menu button to exit menu mode.

Test

Control

Program

Test

Walk Test Silent

Walk Test Audible

Test Fire

Enter Password

0000

Test Fire

Loop 01<>

Test Fire

001

Device 001

Test Fire 001

Start

End

SA-DACT testing

A dialer test is a test of the telephone line for each dialer account. When a dialer

is tested, a normal or abnormal test message (depending on the state of the

system) is sent to the selected account. If the dialer is set up for dual line

operation, a test message is sent to both lines regardless of the success of the

transmission for either account.

Note:

Before conducting a test, configure the dialer’s accounts for proper

operation.

To conduct a dialer test:

1. Press the control panel’s Menu button.
2. Choose Test.
3. Choose Dialer.
4. Enter a level one password.
5. Select the account that you want to test.
6. Press Enter.

Main Menu

Reports

Test

Control

Program

Test

Walk Test Audible

Test Fire

Dialer

Advertising