Edwards Signaling eFSA250 User Manual

Page 120

Advertising
background image

Chapter 2: Front panel programming

108

E-FSA64 and E-FSA250 Technical Reference Manual

• If the system does not have zones, no programming is required in this

section. If the panel is not configured for zone or zone/device reporting,

programming here has no affect on the system except for CMS reporting.

Table 29: Zone programming options

Type

Set the zone type to one of the following values.
Alarm: For circuits with smoke detectors and contact devices.

All activations are immediately considered as alarms. Circuit

cannot be restored until devices are restored to normal and

panel is reset.
Monitor: Monitoring of normally open switches for other

functions (fire door position, etc.). Not approved for use under

ULC 527 in Canada.
Supervisory: For supervisory devices. Momentary activation of

normally open devices immediately places the panel in a

supervisory state and turns on the supervisory LED and relay.
The device types of the devices in a supervisory zone

determine whether the zone is latching or nonlatching. If all

devices in the zone are latching devices, or if you mix latching

and nonlatching devices, the zone will operate as latching.
Waterflow: Activates alarm events when a waterflow switch

closes. Select this zone type when the devices in the zone are

only connected to waterflow switches.

Note:

Do not mix device and zone types. For example, do not

place a nonlatching supervisory device in an alarm zone. When

the supervisory device activates and an alarm event is initiated,

the alarm event automatically clears when the device restores

without having to reset the panel.

Label

Enter a text label for the zone (two lines of 20 characters).

When you have finished, choose Save.

Correlation groups

Enter the number of the correlation group. Choose Yes or No.
• “Yes” adds the item to the group.
• “No” removes the item from the group
When you have finished, choose Save. For more information on

correlation groups, see “What is a correlation group?” on page

32.

Event notification

Set the active, trouble, disable, prealarm, alarm verify,

maintenance alert, and test event information by choosing one

and then setting the notification information. When you have

finished, choose Save. See “Factory default settings” on page

36 for zone event notification default settings.

Note:

If your CMS is set to zone reporting, the event notification

information sent to the receiver comes from the programming in

this section.

Advertising