Chapter 2: Front panel programming

116

E-FSA64 and E-FSA250 Technical Reference Manual

Option

Description

- Loop 1 initializing
- Loop 1 uncfgrd alarm
- Loop 1 map mismatch
- Loop 1 over limits
- Loop 1 device 000
- Loop 1 mapping
- Loop 1 map fault
- Loop 2 initializing
- Loop 2 map mismatch
- Loop 2 over limits
- Loop 2 device 000
- Loop 2 mapping
- Loop 2 map fault
- System startup
- Reset
- Reset/Sil inhibit
- Panel silence
- Program mode
- Signal silence
- Date

- Drill
- Walk test
- Test fire
- Time
- Clear history
- Common alarm
- Common disable
- Common monitor
- Common supervisory
- Common trouble
- Battery charger
- Battery low
- Battery missing
- Local AC power
- System-wide AC power
- Self test fault
- Dialer dsbl/rem disc
- Dialer normal test
- Dialer abnormal test
- Dialer configuration

Event notification

Note:

Programming event notification here is only required if

you selected “Event” as your dialer account or network event

notification setting. See“Dialer programming” on page 117 or

“CMS network (transmitter) programming” on page 120.
Set the alarm, supervisory, monitor, trouble, disable, prealarm,

alarm verify, maintenance alert, and test event information by

choosing one and then setting the notification information.

When you have finished, choose Save. See “Factory default

settings” on page 36 for CMS device event notification default

settings.
Dialer:
• Acct 1 2: Event information is sent to both dialer accounts
• Acct 1: Event information is sent to dialer account one
• Acct 2: Event information is sent to dialer account two
• None: Event information is not sent to the dialer
NET (1-8): Yes or No. Controls whether event information is

sent to the connected network
CID: Contact ID event code (000 to 999)