Edwards Signaling eFSA250 User Manual

Page 217

Advertising
background image

Chapter 5: Diagnostics, maintenance, and testing

E-FSA64 and E-FSA250 Technical Reference Manual

205

• When the device in alarm is removed, the control panel remains in alarm and

a trouble event displays.

• When installed, the new device does not go into alarm, but the LCD displays

a second trouble event when the panel detects the new.

• When the control panel resolves the new device, the alarm condition restores

and the two trouble events clear from the control panel.

Note:

If the device causing the alarm is reinstalled, the device goes into alarm

and the alarm condition does not restore.