Chapter 2: Front panel programming

120

E-FSA64 and E-FSA250 Technical Reference Manual

6. Press the Menu button to exit menu mode, or

continue programming.

Dialer

Type Single Line>

Account 1

Account 2

CMS Device

Swngr Shtdn Rp.200<>

Event Notification

Save

CMS network (transmitter) programming

The information programmed here pertains to the central monitoring station

(CMS) network that the control panel uses to communicate with the CMS. This is

a TCP/IP Ethernet network. Event information is sent to the CMS just as it is

when using a dialer; however, the transmission is over an Ethernet network

rather than the telephone lines.
To program the panel for network reporting, you must install and enable the

optional SA-ETH Ethernet module. Once installed, program only the network

card connected to a compatible network receiver, as listed in the appropriate

compatibility guide.
Obtain the following information from the central monitoring station’s network

administrator:
• An IP address

• Port number

• Receiver number

• Line number

Notes

• CID is the only format that can be transmitted to the CMS over an Ethernet

network.

• You must enter a different port number for each account. If you enter the

same port number for multiple accounts, the panel will enable one account

and disable all others.

• No two accounts can have the same IP address or port number.
• Outputs activation state will not be sent to CMS.

Table 34: CMS network (transmitter) programming options
Option

Description

Enabled

Yes: Enables the CMS network operation
No: Disables the CMS network operation