Edwards Signaling eFSA250 User Manual

Page 66

Advertising
background image

Chapter 2: Front panel programming

54

E-FSA64 and E-FSA250 Technical Reference Manual

Function

Option

Behavior when user key is pressed

Restore

Restores the outputs that belong to the correlation groups

associated with the user key.

Unlatch

Unlatches all latched outputs in the system.

To set up a programmable key:

1. Press the Menu button and choose Program.
2. Choose Programmable Keys.
3. Enter a level two password.
4. Choose the key to be programmed.
5. Choose Edit List or New List. Both commands let

you select a function and edit the list of correlation

groups assigned to the key. The difference

between the two is that:
Edit List lets you makes changes to a key that has

already been programmed. Choose this command

to change the key’s function, or edit the list of

correlation groups assigned to it.

Note:

If you select Edit List for a key that has not

yet been programmed, the message “Nothing to

Edit” is displayed. Choose New List instead.
New List can be used to set up a new

programmable key or to overwrite the current

programming of a key that has already been set

up.

6. Choose a function to assign to the key.

• None

• Activate

• Disable

• Unlatch

• Restore

Note:

To disable a programmed key, choose

None.

Main Menu

Reports

Test

Control

Program

Program

Restore Defaults

RS232 CU Enable

Programmable Keys

Enter Password

0000

Programmable Keys

Key #1

Key #2

Key #1

Edit List

New List

Save

7. If you chose Unlatch in step 6:

Press Enter to reopen the previous menu, and

then choose Save.
— or —

Key #1

Function Unlatch>

<Enter

Advertising