Changing loop configuration options – Edwards Signaling eFSA250 User Manual

Page 97

Advertising
background image

Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

85

Advanced programming for panel and loop options is covered in the following

topics in this chapter.

Programming events

Advanced programming lets you create custom responses to these types of

events:
• Panel events

• Loop events

• Panel event corrs (correlations)
Advanced programming for panel and loop events is covered in the last two

topics in this chapter.

Changing loop configuration options

Loop configuration options

Loop configuration includes the following programmable options:

Table 25: Loop configuration options
Option

Description

Loop class

Indicates whether the loop is wired Class A or Class B.

Zone

Select this option to add a zone.

Correlation Groups

Select this option to add correlation groups.

Device

Select this option to add devices.

Loop 2 Enable [1]

Select Yes to enable Loop 2. Select No to disable Loop 2. [1]

Loop 2 Fst Grp [1] [2]

Select:
001 to 025 to combine loop 1 and 2 devices in the same fast

groups
— or —

101 to 125 to use separate fast groups for Loop 2 devices.

[1] Displayed in dual loop systems only.
[2] See “Programming fast groups for sounder bases” on page 93.

Most options have a factory default setting that you can accept or change.
See “Factory default settings” on page 36.