Loop 2 enable, Zone programming – Edwards Signaling eFSA250 User Manual

Page 119

Advertising
background image

Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

107

Loop 2 enable

If your system is using two device loops (the optional loop expander card is

installed), you must enable the second loop so that it can be programmed.

To enable loop 2:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Loop 2 Enable.
4. Select:

Yes to enable the loop

No to disable the loop

5. Choose Save.
6. Press the Menu button to exit menu mode, or

continue programming.

Loop Configuration

Mapping

Loop 2 Enable Yes>

Save

Loop Configuration

Mapping

Loop 2 Enable Yes>

Save

Selecting loop classes

The loop class must be programmed Class A or Class B based on how the

devices are wired on the loop). The default setting is Class B.

To select a loop class:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Loop Class.
4. Select the loop. If you only have one loop, the loop

is automatically selected.

5. Select either Class A or Class B.
6. Choose Save.
7. Press the Menu button to exit menu mode, or

continue programming.

Loop Configuration

Loop Class

Zone

Correlation Groups

Loop Class

Loop 1 Class A>

Loop 2 Class A>

Save

Loop Class

Loop 1 Class A>

Loop 2 Class A>

Save

Zone programming

Notes

• For background information about zones, see “What is a zone?” on page 32.