Appendix D: Applications

E-FSA64 and E-FSA250 Technical Reference Manual

267

• Do not enable in-suite signal silence.

Floor 1 Correlation
Input

Output

No in-suite

signal silence

Floor 1 dwelling and hallway inputs

Floor 1 dwelling and hallway audibles

Floor 2 Correlation
Input

Output

No in-suite

signal silence

Floor 2 dwelling and hallway inputs

Floor 2 dwelling and hallway audibles

Floor 3 Correlation
Input

Output

No in-suite

signal silence

Floor 3 dwelling and hallway inputs

Floor 3 dwelling and hallway audibles

Floor 4 correlation
Input

Output

No in-suite

signal silence

Floor 4 dwelling and hallway inputs

Floor 4 dwelling and hallway audibles

Floor 5 correlation
Input

Output

No in-suite

signal silence

Floor 5 dwelling and hallway inputs

Floor 5 dwelling and hallway audibles

Creating a hallway correlation

The hallway correlation ensures that an alarm detected anywhere in the building

will turn on all audibles located in hallways throughout the building.
On the input side of this correlation, add all input devices on all floors. Include all

those inside dwelling units and all those in hallways.
On the output side, add all hallway sounders throughout the building.

Notes

• Set the alarm activation count for this correlation to 1.

• Do not enable in-suite signal silence.

Hallway Correlation
Input

Output

Occupant and hallway inputs on all floors

Hallway sounders on all floors