Edwards Signaling eFSA250 User Manual

Page 122

Advertising
background image

Chapter 2: Front panel programming

110

E-FSA64 and E-FSA250 Technical Reference Manual

Notes

• The option “CMS device” is only available if a dialer or network card is

installed

• The option “Printer” is only available if a printer (RS-232) card is installed
• The options “IP”, “MSK”, and “GWY” are only available if a network card is

installed

To program panel configuration options:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Panel Configuration.
4. Program the options.

Main Menu

Reports

Test

Control

Program

Program

Incremental Program

Auto Program

Advanced Program

Advanced Program

Loop Configuration

Panel Configuration

Panel Operation

NAC programming

The NAC circuits connected to the system must be programmed with the type of

NAC, label, correlation groups, and event notification. Each NAC must be

programmed separately.

Table 30: NAC programming options
Option

Description

Class

Select either Class A or Class B.

Note:

NAC 3 and 4 cannot be set to Class A. If NAC 1 and 2

are set to Class A, NAC 3 and 4 automatically configure to

accept the Class A return.