Sa-232 wiring – Edwards Signaling eFSA250 User Manual

Page 33

Advertising
background image

Chapter 1: Installation and wiring

E-FSA64 and E-FSA250 Technical Reference Manual

21

SA-232 wiring

The optional RS-232 card can be wired to a printer to print system events or

wired to a computer to read from and write to the panel using the configuration

utility.

Circuit specifications

• Serial communications

Asynchronous communications maximum resistance: 13 Ω

Maximum capacitance: 0.7 µF

• Wire length: 50 feet max.
• Signal voltage: ± 10 V
• Operating current (standby or alarm): 13 mA nominal, 20 mA max.
• Printer communication speed: 9600 baud
• Power-limited and unsupervised. Supervised when the Supervised Printer

panel programming option is enabled.

Figure 28: SA-232 wiring terminals

GND RTS TXD RXD

Printer wiring
Note:

The printer must be configured through programming for proper operation.

To install wiring to a printer:

1. Locate the serial port on the back of the printer.
2. Connect the DB-25 end of the RS-232 cable to the serial port on the back of

the printer.

3. Connect the other end of the RS-232 cable to the RS-232 card.

Advertising