Chapter 3: System operation

170

E-FSA64 and E-FSA250 Technical Reference Manual

message by selecting Continue to disable the

device or Cancel to exit.
The device is disabled and a message indicating

that the device is disabled is displayed on the

LCD.

9. Press Cancel to return to the previous menu.

— or —
Press the Menu button to exit menu mode.

Device

Loop 01<>

Device Disable<>

001

Device 001

Warning Device Active

Continue?

Cancel?

Disabling and enabling zones

Zones are typically disabled while maintenance is performed to prevent event

messages originating from the zone from being displayed, printed, or reported

off-premises. Disabling a zone does not prevent activations in the zone. All

devices in the zone continue to function normally.

Note:

Remember to enable the zone as soon as you have finished working with

it. Resetting the panel does not restore disabled zones. These must be manually

enabled and then restored.
When you disable a zone:
• The common Disable LED turns on
• On a zone/device system, the LCD displays disabled messages for the zone

and all of the devices in the zone

• On a zone only system, the LCD displays a disabled message for the zone
• The common trouble LED flashes and the panel goes into a trouble state
• The common trouble relay changes state
• The disabled and active points indicators on the LCD increment
• If you are using an LED display expander, the zone LEDs blink for the

disabled zone

• Resetting the panel has no effect on a disabled zone, but removing all power

from the panel enables the zone

• If the zone you are disabling contains devices that are active, a warning

message is displayed