Chapter 2: Front panel programming

70

E-FSA64 and E-FSA250 Technical Reference Manual

Device option Description

Follow

This option controls the conditions that will activate relay or sounder detector

bases. Select from the following values:
Head: The base is controlled by the detector’s settings.
• The base activates when the detector goes into alarm, unless the detector is

set for alarm verification.

• If the detector is set for alarm verification, the base activates when the

detector goes into alarm verification. It does not restore, however, until the

alarm restores.

• The base does not respond when the detector goes into prealarm no matter

how the detector is configured. Also, the base only follows the primary

element of a dual element detector. Any activation from a secondary

element does not trigger the base.

• Devices with the base set to follow Head cannot be placed in correlation

groups. When a device base is set to follow Head, the base is removed as

an output from any Correlation Groups to which it belongs.

Alarm: The base activates its relay when the detector goes into alarm. The base

will not restore until the alarm event has been restored.
Alarm and verify (ALM+VFY): The base activates its relay when the detector

goes into alarm verify and continues when the detector goes into alarm. The

base will not restore until both events have been restored.
Alarm and prealarm (ALM+PALM): The base activates its relay when the

detector goes into prealarm and continues when the detector goes into an alarm.

The base will not restore until both events have been restored.
Riser: The base is triggered individually by the loop controller (sounder bases

only).
None: A correlation group triggers the base. It can be applied to both relay and

sounder bases and is used for relay bases configured as latched output devices.

Incremental programming procedure

Referring to Table 23 on page 69, follow these steps to auto program the panel.

Not all options shown in Table 23 are displayed on all systems.

Notes

• Use the Right or Left Arrow button rather than the Enter button to select

values for each option. The Enter button starts the incremental program

sequence immediately no matter which option the cursor is on.

• The values you select are preserved and will be displayed as defaults the

next time you incrementally program the panel.