Chapter 5: Diagnostics, maintenance, and testing

202

E-FSA64 and E-FSA250 Technical Reference Manual

• Input zones programmed as waterflow with retard require 10 to 15 seconds of

activation to initiate the test signals.

• Devices programmed as alarm verify and not in test mode go directly into

alarm if activated (the alarm verification process is bypassed).

• Restore each device after testing. For example, if you are testing a pull

station, reset the pull station before testing the next device.

The panel terminates walk test if:
• The zone or device being tested remains inactive for 30 minutes.
• The walk test is stopped by the user.

To start a walk test:

1. Press the Menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Enter a level one password.
4. Choose either All Devices or Zone.
5. If you chose Zone, enter the zone ID for the zone

you are going to conduct the walk test.

6. Choose Start.
7. Conduct your walk test.
8. Press Cancel to return to the previous menu.

— or —
Press the Menu button to exit menu mode.

Note:

To see the activation and restoration of all walk

test events, the panel must be reset prior to ending

the walk test. Once the reset is complete, you can

end the walk test and view a walk test report.

Main Menu

Reports

Test

Control

Program

Test

Walk Test Silent

Walk Test Audible

Test Fire

Enter Password

0000

Walk Test Sil/Aud

All Devices

Zone

Zone

Number 01

Zone 01

Start

End

To end a walk test:

1. Press the Menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Choose either All Devices or Zone.
4. If you chose Zone, enter the zone ID of the zone

for which you are going to end the walk test.