Appendix D: Applications

260

E-FSA64 and E-FSA250 Technical Reference Manual

Typical wiring for a local alarm signaling application

The 24 VDC riser that supplies power to the sounder bases is supervised using

an IDC1B Single Input module and a 24 VDC Control Relay.

Figure 57: Typical wiring for a local alarm signaling application

SI

G

+

SI

G

-

D

AT

A-

O

U

T

D

AT

A-

IN

D

AT

A+

IN

/O

U

T

SI

G

+

SI

G

-

D

AT

A-

O

U

T

D

AT

A-

IN

D

AT

A+

IN

/O

U

T

RED
WHT

47 k

EOLR

Double screw

terminal block

(supplied by installer)

12

11

10

9

4

3

2

1 0

8

5 6 7

0 9

1

8

2

7

3

6

4 5

PAM-1

SLC_IN+

SLC_IN-

24 VDC+

24 VDC-

AUX RISER

FIRST DETECTOR

SB4U

LAST DETECTOR

SB4U

BLU
ORG

Programming sounder bases for a local alarm signaling

application

1. Set the panel’s Event Notification option to Device.
2. Configure the smoke detectors as follows.

Device Type: Smoke or Smoke Heat depending on the detector model
Message Line 1: SMOKE_<N>, where <N> can be the device address or

other number

Base Type: Sounder
Follow: Head

3. Configure the IDC1B module as follows:

Device type: Monitor
Message Line 1: 24VDC_RISER