Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

51

Changing the passwords

The second step in programming the panel is to change the level one, level two,

and remote annunciator passwords.

Notes

• We recommend that you change the default passwords before programming

the system.

• The system automatically logs you off after four minutes of inactivity.

To change the passwords:

1. Press the Menu button and choose Program.
2. Choose Password.
3. Enter a level two password.
4. Select the password to be changed: Level 1, Level

2, or Remote (Ann.).

5. Enter the old password and press Enter.
6. Enter the new password and press Enter.
7. Repeat steps 4 through 6 for each password to be

changed.

8. Press the Menu button to exit menu mode, or

continue programming.

Main Menu

Reports

Test

Control

Program

Program

Date and Time

Clear History

Password

Enter Password

0000

Password

Level 1

Level 2

Remote (Ann.)

Enter Old Password

0000

Enter New Password

0000

Restoring the factory default settings

Use the Restore Defaults command to overwrite most custom settings in the

panel, the dialer (CMS network), or both. This lets you commission the panel as

a common alarm system, or remove custom settings in preparation for advanced

programming.