Sa-cla wiring – Edwards Signaling eFSA250 User Manual

Page 35

Advertising
background image

Chapter 1: Installation and wiring

E-FSA64 and E-FSA250 Technical Reference Manual

23

Figure 31: Computer download wiring

RS-232 cable

DB-9 female

Computer

DB-9 COM port

on back of computer

To RS-232 card

Figure 32: Pin designations on female DB-9 plug (back view)

Pin 2 RXD

Pin 3 TXD

Pin 5 COM

Table 6: SA-232 card to computer DB-9 connections
SA-232 card

DB-9

Description [1]

GND

COM (pin 5)

Black wire (ground connection)

RTS

-

Not used

TXD

RXD (pin 2)

White wire (communication)

RXD

TXD (pin 3)

Red wire (communication)

[1] Wire colors refer to Model 260097 RS-232 Cable

SA-CLA wiring

The SA-CLA card is used to supply wiring for Class A NACs and redundant

Class B remote annunciator circuits on eFSA64 control panels.

Circuit specifications

• Operating current

Standby: 3 mA

Alarm: 60 mA max.

• Max. resistance: 26 Ω

• Max. capacitance: 0.35 µF

• Max. current: 2.5 A per circuit