Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

103

Note:

Depending on the type of device you are

programming, some of the options in the table

below may not be available.

7. When you finish programming an option, choose

Save, then choose the next option.

8. Press the Menu button to exit menu mode, or

continue programming.

Save

Device 001

Base Follow Device<>

Type Smoke<>

Save

Programming relay and sounder detector bases

Relay and sounder bases require some configuration not required by other

devices. First, the panel does not automatically distinguish between relay and

sounder bases — Both are set by default to base type “relay”. You must

manually change this setting for sounder bases.
In addition, configuration is required to control how these devices are activated.

Relay bases can be activated by:
• The detector to which they are attached

• One or more correlation groups
Sounder bases can be activated by:
• The detector to which they are attached

• One or more correlation groups

• The 24 volt riser
You can configure these options using the procedure given below. See Table 26

on page 95 for information on the Base and Follow options.