Auxiliary/smoke power output wiring – Edwards Signaling eFSA250 User Manual

Page 28

Advertising
background image

Chapter 1: Installation and wiring

16

E-FSA64 and E-FSA250 Technical Reference Manual

Figure 22: Annunciator channel wiring (Class A)

+

TB4

+

Channel 1 Channel 2

CH1 (+) IN
CH1 ( ) IN

CH2 (+) IN
CH2 ( ) IN

Annunciator

Note:

To use the Class A option, you must install the SA-CLA module in the eFSA64.

Figure 23: Annunciator channel wiring (Class B)

+

TB4

+

Channel 1 Channel 2

CH1 (+) IN
CH1 ( ) IN

CH2 (+) IN
CH2 ( ) IN

Annunciator

Auxiliary/smoke power output wiring

The control panel provides resettable and continuous AUX power output circuits.

Use the resettable AUX power output for devices such as four-wire detectors or

beam detectors. Use the continuous AUX power output for devices such as

remote annunciators or door holders.

Notes

• If you do not need resettable AUX power, you can configure the resettable

AUX power output to supply continuous power.

• For a complete list of devices that can be connected to this circuit, refer to the

eFSA64 and eFSA250 Series Compatibility List (P/N 3101199).

Advertising
This manual is related to the following products: