Chapter 3: System operation

144

E-FSA64 and E-FSA250 Technical Reference Manual

System LEDs

LEDs indicate system events and system operation.

Table 38: System LEDs
LED

Description

Alarm

Red LED. Flashes when there is an active alarm event on any

loop. On steady once acknowledged.

Trouble

Yellow LED. Flashes when there’s a fault with a monitored

circuit or system component or when a circuit is disabled. On

steady once acknowledged.

Sup (Supervisory)

Yellow LED. Flashes when there is an active supervisory event

on any loop. On steady once acknowledged.

AC Power

Green LED. On when the panel has AC power.

Disable

Yellow LED. Double-flashes when there is a disabled circuit or

alarm relay.

Ground Fault

Yellow LED. On steady during an active ground fault.

Test

Yellow LED. Flashes when performing an audible walk test.

Steady indicates a silent test.

Service Detector

Yellow LED. Indicates that detector needs servicing.

Signal Silence

Yellow LED. On steady indicates that NAC circuits are turned

off but the panel is still in alarm.

Remote Disconnect

Yellow LED. On steady indicates that the CMS devices (dialer

and network card) are disabled or that the alarm relay is

enabled or disabled when the dialer is set to modem only.

User keys

Yellow LED. Indicates that the programmed key function is

active.

LED display expander LEDs


The D16L-Fa LED Display Expander provides LED annunciation for up to 16

zones. The expander provides two LEDs for each zone. You can install two

display expanders in the panel.

LED operation zones 1 through 12

(Also applies to zones 17 through 28 if the second LED expander is installed.)
• LED 1 - Alarm: Red LED flashes